Bosch Appliances D6600 12.4.5, Configuring for Network Communication, Default, Valid Values

Models: D6600

1 88
Download 88 pages 54.03 Kb
Page 63
Image 63
12.4.5

Conettix Communications Receiver/

Network Communications en 63

Gateway

 

 

 

Config

Config

Config

Default

Valid Values

Description

Section

Sub-

Parameter

Value

 

 

 

section

 

 

 

 

 

 

 

 

 

 

bosch tunnel

1 or 2

aes key

01020304

16 to 32

Enter the 16 to 32 Hexadecimal characters

 

 

 

05060708

Hexadecimal

depending upon the Key size entered:

 

 

 

09101112

characters

128-bit requires 16 Hex characters

 

 

 

13141516

 

192-bit requires 24 Hex characters

 

 

 

 

 

256-bit requires 32 Hex characters

 

 

 

 

 

 

xml import

 

reboot

enable

enable, disable

DO NOT CHANGE. This instructs the module

control

 

 

 

 

to reboot after the parameters are loaded

 

 

 

 

 

into the device to begin using the new

 

 

 

 

 

configuration. Eliminates the need to cycle

 

 

 

 

 

power to the device. If this is changed from

 

 

 

 

 

enabled, it will require a power cycle for the

 

 

 

 

 

new configuration to take effect.

 

 

 

 

 

 

Table 12.1: XML Configuration Parameters

 

 

 

1.Click Save XML As to save the changes, and then enter a name for these configuration settings.

2.Click Send XML to send these changes to the D6100IPv6. The device saves the changes and reboots with the new configuration.

3.Disconnect the Ethernet cable connecting the computer and the D6100IPv6, and then connect the D6100IPv6 to the network switch or router as required.

 

Notice!

i

The D6100IPv6 Ethernet module is a Lantronix Xport Pro with custom firmware installed and

UL Listed for use on the D6100IPv6. If standard Lantronix firmware is installed on a

 

 

D6100IPv6, the device no longer functions correctly.

 

 

12.4.5

Configuring for Network Communication

 

The following steps allow the D6100IPv6 to communicate with the host computer running the

 

D6200 Programming Software.

 

 

 

Notice!

i

For the network communication to function, install a properly configured D6100IPv6. Refer to

the previous sections. If network communications are not installed, further D6200 software

 

 

programming using the network is not possible.Consequences

 

 

 

 

1.

On the D6100IPv6 keypad, press Menu and enter the default passcode of [6][1][0][0] to

 

 

enter the programming mode. Press Menu again.

 

 

 

Notice!

i

To change any programming parameter, follow this syntax:

Press Enter.

 

Enter the desired value.

 

Press Enter again to store the value.

 

 

 

2. Press Down until viewing 6 NETWORK CONFIGURATION, and then press Enter.

 

3.

Press Down until viewing 6.2 Network adapter, and then press Enter.

Bosch Security Systems, Inc.

Installation and Operation Guide

2012.11 08 4998122704

Page 63
Image 63
Bosch Appliances D6600 12.4.5, Configuring for Network Communication, Default, Valid Values, Description, Section, section