Bosch Appliances D6600 No Data Received Reports, 13.1, 13.2, Data Error, 13.3, Wrong Data

Models: D6600

1 88
Download 88 pages 54.03 Kb
Page 72
Image 72
No Data Received Reports

72 en No Data Received Reports

Conettix Communications Receiver/

Gateway

 

 

 

13

No Data Received Reports

 

If a message is garbled (incorrect checksum or inconsistent message rounds) due to a noisy

 

telephone line or other difficulty, the receiver withholds the kiss-off tone. This causes the

 

control panel to send the same message again up to four times.

13.1

No Data Received

 

The D6600/D6100IPv6 generates one or more of the following events:

 

– Telephone line noise causes the data to be unrecognized.

 

– A control panel sends the data in a format not recognized by the D6600/D6100IPv6.

 

– A control panel transmitted nothing.

 

Figure 13.1: No Data Received Message

13.2

Data Error

 

Data Error is a function of PSTN. It is an error condition when the D6600/D6100IPv6 receives

 

partial data, appears on the LCD, and sends the error to a connected printer.

 

This occurs when telephone line noise causes data to be unrecognizable.

13.3

Wrong Data

Wrong Data is a function of the CPU where the PSTN software sends an invalid signal to the CPU. It only sends output to the LCD and any connected printer.

2012.11 08 4998122704

Installation and Operation Guide

Bosch Security Systems, Inc.

Page 72
Image 72
Bosch Appliances D6600 installation and operation guide No Data Received Reports, 13.1, 13.2, Data Error, 13.3, Wrong Data