![Fig. 11—Horizontal Right Tube Configuration](/images/new-backgrounds/47908/4790827x1.webp)
| CAP | COLLECTOR BOX DRAIN TUBE (BLUE) |
| COLLECTOR BOX TUBE (GREEN) | |
|
| |
PLUG |
| COLLECTOR BOX EXTENSION TUBE |
| COLLECTOR BOX TUBE (PINK) | |
|
|
AUXILARY “J” BOX RELOCATED HERE |
CONDENSATE |
TRAP |
COLLECTOR BOX DRAIN TUBE |
(BLUE AND WHITE STRIPED) |
INDUCER HOUSING
DRAIN TUBE (VIOLET)
COLLECTOR BOX
EXTENSION TUBE
A00214
Fig. 11—Horizontal Right Tube Configuration
b.Install removed clamp and plug into UPPER collector box drain tube (blue label) which was previously connected to condensate trap.
c.Connect LOWER collector box drain tube (blue and white striped label) to condensate trap. Tube does not need to be cut.
d.Clamp tube to prevent any condensate leakage.
2.Inducer Housing Drain Tube:
a.Remove
b.Remove and discard UPPER (molded) inducer housing drain tube which was previously connected to condensate trap.
c.Install cap and clamp on UPPER inducer housing drain connection where molded drain tube was removed.
d.Use inducer housing drain extension tube (violet label and
e.Determine appropriate length, cut, and connect tube to condensate trap.
f.Clamp tube to prevent any condensate leakage.
3.Relief Port Tube
Refer to Pressure Switch Tubing section for connection procedure.
C. Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
D. Pressure Switch Tubing
One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW or HORIZONTAL LEFT applications. This tube MUST be disconnected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZONTAL RIGHT applications.
NOTE: See Fig. 11 or tube routing label on main furnace door to check for proper connections. Relocate tubes as described below.
1.Disconnect collector box pressure tube (pink label) attached to pressure switch.
2.Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connection by splicing to small diameter tube
3.Connect collector box pressure tube (green label) to High Pressure Switch connection labeled COLLECTOR BOX.
4.Use remaining smaller diameter tube
5.Route this extended tube (pink label) to condensate trap relief port connection.