Fig. 31—Control Center
EAC1
EAC2
A93053
Fig. 32—EAC Terminals on Control Center
4.Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so appliance shall operate continuously.
5.Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
6.After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other
7.If improper venting is observed during any of above tests, the venting system must be corrected.
Vent system or vent connectors may need to be resized. For any other appliances when resizing vent systems or vent connectors, system or connector must be sized to approach minimum size as determined using appropriate table found in the NFGC or NSCNGPIC.
B. Combustion-Air and Vent Piping
GENERAL
In Canada, construct all