Bryant 355MAV instruction manual MaximumCapacity of Pipe, TypicalGas Pipe Arrangement

Models: 355MAV

1 60
Download 60 pages 27.74 Kb
Page 24
Image 24
Table 3—Maximum Capacity of Pipe*

Table 3—Maximum Capacity of Pipe*

NOMINAL

 

 

 

LENGTH OF PIPE (FT)

 

 

IRON

INTERNAL

 

 

 

 

 

 

 

 

 

 

 

PIPE

DIAMETER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIZE

(IN.)

10

20

 

30

 

40

50

(IN.)

 

 

 

 

 

 

 

 

 

 

 

1/2

0.622

175

120

 

97

 

82

73

3/4

0.824

360

250

 

200

 

170

151

1

1.049

680

465

 

375

 

320

285

1-1/4

1.380

1400

950

 

770

 

660

580

1-1/2

1.610

2100

1460

 

1180

 

990

900

 

 

 

 

 

 

 

 

 

*Cubic ft of gas per hr. for gas pressures of 0.5 psig (14–in. wc) or less and a pressure drop of 0.5–in wc (based on a 0.60 specific gravity gas). Ref: NFGC.

Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to propane gas.

CAUTION: Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls.

Fig. 26—Typical Gas Pipe Arrangement WARNING: Gas valve shutoff switch MUST be facing forward or tilted upward. Failure to follow this warning could result in property damage or death.

Manual background WARNING: Never purge a gas line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for purpose of checking leakage. Use a soap-and-water solution to check for leakage. Failure to follow this warning could result in fire, explosion, personal injury, or death.

Manual background WARNING: Use proper length of pipe to avoid stress on gas control manifold. Failure to follow this warning could result in a gas leak resulting in fire, explosion, personal injury, or death.

Install a sediment trap in riser leading to furnace. Trap can be installed by connecting a tee to riser leading to furnace so straight-through section of tee is vertical. Then connect a capped nipple into lower end of tee. Capped nipple should extend below level of gas controls. Place a ground joint union between gas control manifold and manual gas shutoff valve. (See Fig. 26.)

GAS

SUPPLY

MANUAL

SHUTOFF VALVE Manual backgroundManual backgroundManual backgroundManual background (REQUIRED) Manual backgroundManual backgroundManual background

SEDIMENT

TRAP

UNION

A93324

Fig. 26—Typical Gas Pipe Arrangement

Manual background CAUTION: If a flexible connector is required or allowed by authority having jurisdiction, black iron pipe shall be installed at gas valve and extend a minimum of 2 in. outside furnace casing.

An accessible manual shutoff valve MUST be installed upstream of furnace gas controls and within 6 ft of furnace. A 1/8-in. NPT plugged tapping, accessible for test gage connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff valve.

—24—

Page 24
Image 24
Bryant 355MAV instruction manual MaximumCapacity of Pipe, TypicalGas Pipe Arrangement