Bryant 355MAV MaximumAllowable Pipe Length ft, Combustion-Airand Vent Pipe Attachment

Models: 355MAV

1 60
Download 60 pages 27.74 Kb
Page 34
Image 34
Table 7—Maximum Allowable Pipe Length (ft)

Table 7—Maximum Allowable Pipe Length (ft)

ALTITUDE (FT)

UNIT SIZE

TERMINATION

PIPE DIA

 

 

NUMBER OF 90° ELBOWS

 

TYPE

(IN.)*

1

2

 

3

4

 

5

6

 

 

 

 

 

042040

2 Pipe or 2-in

1-1/2

50

45

 

40

35

 

30

25

 

Concentric

2

70

70

 

70

70

 

70

70

 

 

 

 

 

042060

2 Pipe or 2-in

1-1/2

50

45

 

40

35

 

30

25

 

Concentric

2

70

70

 

70

70

 

70

70

 

 

 

 

 

042080

2 Pipe or 2-in

1-1/2

30

25

 

20

15

 

10

5

0 to 2000

060080

Concentric

2

70

70

 

70

70

 

70

70

 

060100

2 Pipe or 2-in

2

45

40

 

35

30

 

25

20

 

Concentric

2-1/2

70

70

 

70

70

 

70

70

 

 

 

 

 

 

2 Pipe or 3-in.

2-1/2

10

NA

 

NA

NA

 

NA

NA

 

060120

3

35

30

 

15

NA

 

NA

NA

 

Concentric

 

 

 

 

3†

70

70

 

70

70

 

70

70

 

 

 

 

 

ALTITUDE (FT)

UNIT SIZE

TERMINATION

PIPE DIA

 

 

NUMBER OF 90° ELBOWS

 

 

TYPE

(IN.)*

1

2

 

3

4

 

5

6

 

 

 

 

 

042040

2 Pipe or 2-in

1–1/2

45

40

 

35

30

 

25

20

 

Concentric

2

70

70

 

70

70

 

70

70

 

 

 

 

 

042060

2 Pipe or 2-in

1–1/2

45

40

 

35

30

 

25

20

 

Concentric

2

70

70

 

70

70

 

70

70

 

 

 

 

2001 to 3000

042080

2 Pipe or 2-in

1–1/2

26

21

 

16

11

 

6

NA

060080

Concentric

2

70

70

 

70

70

 

70

70

 

 

 

 

060100

2 Pipe or 2-in

2

40

35

 

30

25

 

20

15

 

Concentric

2–1/2

70

70

 

70

70

 

70

70

 

 

 

 

 

060120

2 Pipe or 3-in.

3

31

26

 

12

NA

 

NA

NA

 

Concentric

3†

63

62

 

62

61

 

61

61

 

 

 

 

ALTITUDE (FT)

UNIT SIZE

TERMINATION

PIPE DIA

 

 

NUMBER OF 90° ELBOWS

 

 

TYPE

(IN.)*

1

2

 

3

4

 

5

6

 

 

 

 

 

042040

2 Pipe or 2-in

1-1/2

42

37

 

32

27

 

22

17

 

Concentric

2

70

70

 

70

70

 

70

70

 

 

 

 

 

042060

2 Pipe or 2-in

1-1/2

42

37

 

32

27

 

22

17

 

Concentric

2

70

70

 

70

70

 

70

70

 

 

 

 

3001 to 4000

042080

2 Pipe or 2-in

1-1/2

25

20

 

15

10

 

5

NA

060080

Concentric

2

70

70

 

70

70

 

70

70

 

 

 

 

060100

2 Pipe or 2-in

2

38

33

 

28

23

 

18

13

 

Concentric

2-1/2

70

70

 

70

70

 

70

70

 

 

 

 

 

060120

2 Pipe or 3-in.

3

29

24

 

10

NA

 

NA

NA

 

Concentric

3†

59

59

 

58

57

 

57

56

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See notes at end of table.

NOTE: Do not count elbows or pipe sections in terminations or within furnace. See shaded areas in Fig. 40, 41, 42, 43, and 44.

EXAMPLE: An 042080 size furnace located in Indianapolis, elevation 650 ft above sea level, could be installed in an application requiring 3 elbows and 17 ft of vent pipe, along with 5 elbows and 16 ft of combustion-air pipe. Table 7 indicates this application would allow a 1-1/2-in. diameter vent pipe, but require a 2-in. diameter combustion air pipe (1-1/2-in. pipe is good for 20 ft with 3 elbows, but only 10 ft with 5 elbows). Therefore, 2-in. diameter pipe must be used for both vent and combustion-air pipes since larger required diameter must always be used for both pipes. If same installation were in Albuquerque, elevation 5250 ft above sea level, installation would require 2-in. vent pipe and combustion-air pipe. At 5001- to 6000-ft elevation, 1-1/2-in. pipe is not allowed with 5 elbows, but 2-in. pipe is good for 68 ft with 5 elbows.

COMBUSTION-AIR AND VENT PIPE ATTACHMENT

NOTE: All pipe joints must be watertight except attachment of combustion-air pipe to inlet housing connection, since it may be necessary to remove pipe for servicing.

1.Attach combustion-air pipe to furnace as follows:

a.Determine location of combustion-air intake pipe connection to combustion-air intake housing as shown in Fig. 36 for application.

b.Reposition combustion-air intake housing plug fitting in appropriate unused intake housing connection.

c.If required, insert perforated disk assembly (factory-supplied in loose parts bag) in intake housing where combustion-air intake pipe will be connected. If half disk set is required, install with shoulder of disk against stop in combustion-air inlet.

d.Install pipe support (factory-supplied in loose parts bag) into selected furnace casing combustion-air pipe hole. Pipe support should be positioned at bottom of casing hole.

e.Insert 2-in. diameter pipe into intake housing.

f.Install casing hole filler cap (factory-supplied in loose parts bag) in unused combustion-air pipe casing hole.

—34—

Page 34
Image 34
Bryant 355MAV instruction manual MaximumAllowable Pipe Length ft, Combustion-Airand Vent Pipe Attachment