Bryant 355MAV instruction manual AmpDraw Check with Ammeter, PROCEDURE 7-CHECKLIST

Models: 355MAV

1 60
Download 60 pages 27.74 Kb
Page 58
Image 58
Fig. 59—Amp Draw Check with Ammeter

THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC.,

MUST BE OUT OF CIRCUIT.)

HOOK-AROUND AMMETER

R Y W G

10 TURNSPROCEDURE 7—CHECKLIST

Manual backgroundFROM UNIT 24-V

CONTROL TERMINALS

EXAMPLE:

5.0 AMPS ON AMMETER

=

0.5 AMPS FOR THERMOSTAT

10 TURNS AROUND JAWS

ANTICIPATOR SETTING

 

 

A96316

Fig. 59—Amp Draw Check with Ammeter

3.Turn on 115-v power to furnace.

4.Set thermostat to call for heat. When pressure switches are functioning properly, fault code 42 will flash on control center approximately 10 sec after thermostat switch is closed. If either a fault code 31 or 32 is flashed when ICM inducer motor is disconnected, the furnace will shut itself down immediately. Determine the reason pressure switches did not function properly and correct the condition.

5.Turn off 115-v power to furnace.

6.Reconnect inducer motor wire harness. Reinstall furnace access door.

7.Turn on 115-v power to furnace.

8.Reset thermostat to desired temperature.

PROCEDURE 7—CHECKLIST

1.Put away tools and instruments. Clean up debris.

2.Verify manual reset switch has continuity.

3.Verify that blower and control access doors are properly installed.

4.Cycle test furnace with room thermostat.

5.Check operation of accessories per manufacturer’s instructions.

6.Review User’s Guide with owner.

7.Leave literature packet near furnace.

—58—

Page 58
Image 58
Bryant 355MAV instruction manual AmpDraw Check with Ammeter, PROCEDURE 7-CHECKLIST