Table
ALTITUDE (FT) | UNIT SIZE | TERMINATION | PIPE DIA |
|
| NUMBER OF 90° ELBOWS |
| ||||
TYPE | (IN.)* | 1 | 2 |
| 3 | 4 |
| 5 | 6 | ||
|
|
|
| ||||||||
| 042040 | 2 Pipe or | 30 | 25 |
| 20 | 15 |
| 10 | 5 | |
| Concentric | 2 | 62 | 60 |
| 58 | 56 |
| 55 | 53 | |
|
|
|
| ||||||||
| 042060 | 2 Pipe or | 30 | 25 |
| 20 | 15 |
| 10 | 5 | |
| Concentric | 2 | 62 | 60 |
| 58 | 56 |
| 55 | 53 | |
|
|
|
| ||||||||
8001 to 9000‡ | 042080 | 2 Pipe or | 17 | 12 |
| 7 | NA |
| NA | NA | |
060080 | Concentric | 2 | 62 | 60 |
| 58 | 56 |
| 51 | 46 | |
|
|
| |||||||||
| 060100 | 2 Pipe or | 2 | 27 | 22 |
| 17 | 12 |
| 7 | NA |
| Concentric | 62 | 60 |
| 58 | 56 |
| 55 | 53 | ||
|
|
|
| ||||||||
| 060120 | 2 Pipe or | 3† | 43 | 41 |
| 39 | 37 |
| 35 | 34 |
| Concentric |
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |
ALTITUDE (FT) | UNIT SIZE | TERMINATION | PIPE DIA |
|
| NUMBER OF 90° ELBOWS |
|
| |||
TYPE | (IN.)* | 1 | 2 |
| 3 | 4 |
| 5 | 6 | ||
|
|
|
| ||||||||
| 042040 | 2 Pipe or | 27 | 22 |
| 17 | 12 |
| 7 | NA | |
| Concentric | 2 | 57 | 55 |
| 53 | 51 |
| 49 | 47 | |
|
|
|
| ||||||||
| 042060 | 2 Pipe or | 27 | 22 |
| 17 | 12 |
| 7 | NA | |
| Concentric | 2 | 57 | 55 |
| 53 | 51 |
| 49 | 47 | |
|
|
|
| ||||||||
9001 to 10,000‡ | 042080 | 2 Pipe or | 15 | 10 |
| 5 | NA |
| NA | NA | |
060080 | Concentric | 2 | 57 | 55 |
| 53 | 51 |
| 46 | 41 | |
|
|
| |||||||||
| 060100 | 2 Pipe or | 2 | 24 | 19 |
| 14 | 9 |
| NA | NA |
| Concentric | 57 | 55 |
| 53 | 51 |
| 49 | 47 | ||
|
|
|
| ||||||||
| 060120 | 2 Pipe or | 3 | 39 | 37 |
| 35 | 33 |
| 31 | 29 |
| Concentric |
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
Disk
‡Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction.
NOTES:
1.Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
2.Size both the
3.Assume two 45° elbows equal one 90° elbow. Long radius elbows are desirable and may be required in some cases.
4.Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5.The minimum pipe length is 5 ft for all applications.
If use of this drain connection is desired, drill out fitting’s tap plug with a
| COMBUSTION AIR |
3/8" ID TUBE | INTAKE HOUSING |
BURNER | |
| BOX |
3/16"
DRILL
TRAP
TO OPEN
DRAIN
COMBUSTION
AIR PIPE
4″
(102mm)
MIN
A93035
Fig. 38—Intake Housing Plug Fitting Drain
2.Attach vent pipe to furnace as follows:
a.Determine location of vent pipe connection to inducer housing as shown in Fig. 36 for application.
b.Reposition elastomeric (rubber) inducer housing outlet cap and clamp to appropriate unused inducer housing connection. Tighten clamp.
WARNING: Inducer housing outlet cap must be installed and fully seated against inducer housing. Clamp must be tightened to prevent any condensate leakage. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.
c.Install pipe support