Bryant 355MAV instruction manual PROCEDURE 8-ELECTRICALCONNECTIONS, A. 115-VWiring

Models: 355MAV

1 60
Download 60 pages 27.74 Kb
Page 25
Image 25
PROCEDURE 8—ELECTRICAL CONNECTIONS

NOTE: The gas valve inlet press tap connection is suitable to use as test gage connection providing test pressure DOES NOT exceed maximum

0.5psig (14-in. wc) stated on gas valve. (See Fig. 56.) Piping should be pressure tested in accordance with NFGC local and national plumbing and gas codes before furnace is attached. In Canada, refer to current edition of NSCNGPIC. If pressure exceeds 0.5 psig (14-in. wc), gas supply pipe must be disconnected from furnace and capped before pressure test. If test pressure is equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff switch located on gas valve before test. It is recommended that ground joint union be loosened before pressure testing. After all connections have been made, purge lines and check for leakage.

 

 

 

 

 

 

 

 

FIELD 24-V WIRING

 

 

 

 

 

 

 

 

FIELD 115-, 208/230-, 460-V WIRING

 

 

 

 

 

 

 

 

FACTORY 24-V WIRING

 

 

 

 

 

 

 

 

FACTORY 115-, 208/230-, 460-V WIRING

 

 

NOTE 5

 

 

 

 

 

THERMOSTAT

 

 

FIVE

 

W

C

R

G

Y

FIELD-SUPPLIED

 

 

TERMINALS

 

WIRE

 

 

 

 

 

 

 

DISCONNECT

 

THREE-WIRE

 

 

 

 

 

 

 

 

 

HEATING

 

 

 

 

 

 

 

208/230- OR

 

ONLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460-V

 

 

W/W1

 

 

 

 

 

 

THREE PHASE

 

 

 

 

 

 

 

 

 

115-V

 

 

NOTE

 

 

 

 

GND

GND

 

W2

 

 

 

 

 

 

 

 

 

 

 

 

SINGLE

 

 

3

 

 

 

 

 

 

PHASE

 

R

 

 

 

 

 

 

208/230-V

 

 

 

 

 

 

 

 

 

 

AUXILIARY

G

 

 

 

 

 

 

SINGLE

115-V

 

 

 

 

 

 

 

PHASE

FIELD-SUPPLIED

J-BOX

C

 

NOTE 1

 

GND

GND

DISCONNECT

 

 

 

 

CONDENSING

SWITCH

 

Y/Y2

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

24-V

 

 

 

TWO WIRE

 

 

FURNACE

TERMINAL

 

 

 

 

 

 

CONTROL

BLOCK

 

 

NOTES:

 

 

 

CENTER

 

 

 

 

 

 

 

 

 

1. Connect Y or Y/Y2 terminal as shown for proper cooling operation.

 

 

 

 

 

 

 

 

 

 

2. Proper polarity must be maintained for 115-v wiring.

 

 

 

 

 

3. Use W2 with 2-stage thermostat when zoning.

 

 

 

 

 

4. If any of the original wire, as supplied, must be replaced, use

 

 

 

 

 

 

same type or equivalent wire.

 

 

 

 

 

 

5. Some thermostats require a "C" terminal connection as shown.

A98325

Fig. 27—Heating and Cooling Application Wiring Diagram

PROCEDURE 8—ELECTRICAL CONNECTIONS

See Fig. 27 for field wiring diagram showing typical field 115-v and 24-v wiring. Check all factory and field electrical connections for tightness.

A. 115-V Wiring WARNING: Blower access panel door switch opens 115-v power to control center. No component operation can occur. Do not bypass or close switch with panel removed. Failure to follow this warning could result in personal injury or death.

Manual background CAUTION: Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green wire routed to gas valve and burner box screw.

A. 115-V Wiring

Before proceeding with electrical connections, make certain that voltage, frequency, and phase correspond to that specified on the furnace rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 4 for equipment electrical specifications.

Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70-2002 and any local codes or ordinances that might apply. For Canadian installations, all electrical connections must be made in accordance with Canadian Electrical Code CSA C22.1 or authorities having jurisdiction.

Use a separate, fused branch electrical circuit containing a properly sized fuse or circuit breaker for this furnace. See Table 4 for wire size and fuse specifications. A disconnecting means must be located within sight from and readily accessible to furnace.

NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control LED status indicator light will flash rapidly and furnace will NOT operate.

—25—

Page 25
Image 25
Bryant 355MAV instruction manual PROCEDURE 8-ELECTRICALCONNECTIONS, A. 115-VWiring