Bryant 355MAV LOCATION PROCEDURE 1-GENERAL, FurnaceLocation for Proper Condensate, Drainage

Models: 355MAV

1 60
Download 60 pages 27.74 Kb
Page 15
Image 15
LOCATION

6.Determine appropriate length, cut, and connect tube.

7.Clamp tube to relief port connection.

E. Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommendations and procedures

F. Construct a Working Platform

Construct working platform where all required furnace clearances are met. (See Fig. 3 and 10.)

Fig. 12—Furnace Location for Proper Condensate CAUTION: The condensate trap MUST be installed below furnace. See Fig. 4 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.

NOTE: Combustion-air and vent pipes are restricted to a minimum length of 5 ft. (See Table 6.)

NOTE: A 12-in. minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 10 or 29.)

LOCATION

PROCEDURE 1—GENERAL

When a furnace is installed so that supply ducts carry air to areas outside the space containing the furnace, return air must also be handled by ducts sealed to furnace casing. The ducts terminate outside the space containing the furnace to ensure there will not be a negative pressure condition within equipment room or space. Furnace may be located in a confined space without special provisions for dilution or ventilation air. This furnace must be installed so electrical components are protected from water.

LEVEL (0)￿ FRONT TO￿

12MAX

LEVEL (0)￿

TO￿

12MAX

FRONT

UPFLOW OR DOWNFLOW

HORIZONTAL

A93025

Fig. 12—Furnace Location for Proper Condensate

Drainage

NOTE: For proper furnace operation, install furnace so that it is level or pitched forward within 1/2-in. to ensure proper condensate drainage from secondary heat exchangers. (See Fig. 12.)

NOTE: These furnaces are designed for a minimum continuous return-air temperature of 60°F or intermittent operation down to 55°F such as when used with a night setback thermostat. Return-air temperature must not exceed a maximum of 85°F. Failure to follow these return-air temperature limits may affect reliability of heat exchangers, motors, and controls. (See Fig. 13.)

A93042

Fig. 13—Return-Air Temperature

Locate furnace as close to center of air distribution system as possible.

Locate furnace so combustion-air pipe lengths are not exceeded. Refer to Table 6.

—15—

Page 15
Image 15
Bryant 355MAV LOCATION PROCEDURE 1-GENERAL, FurnaceLocation for Proper Condensate, Drainage, Return-AirTemperature