a.Connect relief port tube (green label) to condensate trap.
b.Extend this tube (if required) by splicing to small diameter tube
c.Determine appropriate length, cut, and connect tube.
E. Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
F. Pressure Switch Tubing
The LOWER collector box pressure tube (pink label) is factory connected to the High Pressure Switch and should not require any modification. NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.
G. Upper Collector Box and Inducer Housing (Unused) Drain Connections
1.Upper Collector Box Drain Connection
Attached to the UPPER collector box drain connection is a
NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.
2.Upper Inducer Housing Drain Connection
Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.
NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.
H. Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations and procedures.
PROCEDURE 3—DOWNFLOW APPLICATIONS
A downflow furnace application is where furnace blower is located above combustion and controls section of furnace, and conditioned air is discharged downwards.
COLLECTOR BOX
DRAIN TUBE (BLUE)
CAP
PLUG
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)
COLLECTOR BOX EXTENSION TUBE
CONDENSATE
TRAP
INDUCER HOUSING
DRAIN TUBE (VIOLET)
A94215
Fig. 7—Downflow Tube Configuration
(Left-Hand Trap Installation)
A. Condensate Trap Location
The condensate trap must be removed from the
To relocate condensate trap from the blower shelf to desired location, perform the following: