Bryant 355MAV E. Condensate Trap Field Drain Attachment, F. Pressure Switch Tubing

Models: 355MAV

1 60
Download 60 pages 27.74 Kb
Page 9
Image 9
E. Condensate Trap Field Drain Attachment

a.Connect relief port tube (green label) to condensate trap.

b.Extend this tube (if required) by splicing to small diameter tube (factory-supplied in loose parts bag).

c.Determine appropriate length, cut, and connect tube.

E. Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

F. Pressure Switch Tubing

The LOWER collector box pressure tube (pink label) is factory connected to the High Pressure Switch and should not require any modification. NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.

G. Upper Collector Box and Inducer Housing (Unused) Drain Connections

1.Upper Collector Box Drain Connection

Attached to the UPPER collector box drain connection is a factory-installed corrugated, plugged tube (blue and white striped label). This tube is plugged to prevent condensate leakage in this application. Ensure this tube is plugged.

NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.

2.Upper Inducer Housing Drain Connection

Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.

NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.

H. Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommendations and procedures.

PROCEDURE 3—DOWNFLOW APPLICATIONS

A downflow furnace application is where furnace blower is located above combustion and controls section of furnace, and conditioned air is discharged downwards.

COLLECTOR BOX￿

DRAIN TUBE (BLUE)

CAP

PLUG

COLLECTOR BOX￿

TUBE (GREEN)

COLLECTOR BOX￿

TUBE (PINK)

COLLECTOR BOX￿ DRAIN TUBE (BLUE￿ & WHITE STRIPED)

COLLECTOR BOX ￿ EXTENSION TUBE

CONDENSATE￿

TRAP

INDUCER HOUSING ￿

DRAIN TUBE (VIOLET)

A94215

Fig. 7—Downflow Tube Configuration

(Left-Hand Trap Installation)

A. Condensate Trap Location

The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2, 7, or 8.

To relocate condensate trap from the blower shelf to desired location, perform the following:

—9—

Page 9
Image 9
Bryant 355MAV E. Condensate Trap Field Drain Attachment, F. Pressure Switch Tubing, H. Condensate Trap Freeze Protection