BURNER FLAME

BURNER

MANIFOLD

A89020

Fig. 58—Burner Flame

EXAMPLE:

100,000 Btuh input furnace installed at 4300 ft.

Furnace Input Rate

 

Derate

 

Furnace Input Rate

X

Multiplier

=

at Installation

at Sea Level

 

Factor

 

Altitude

 

 

 

100,000

X

0.91

=

91,000

 

 

 

 

 

Table 14—Altitude Derate Multiplier for U.S.A.

ALTITUDE

PERCENT

DERATE MULTIPLIER

(FT)

OF DERATE

FACTOR FOR U.S.A.*

0–2000

0

1.00

2001–3000

4–6

0.95

3001–4000

6–8

0.93

4001–5000

8–10

0.91

5001–6000

10–12

0.89

6001–7000

12–14

0.87

7001–8000

14–16

0.85

8001–9000

16–18

0.83

9001–10,000

18–20

0.81

* Derate multiplier factor is based on midpoint altitude for altitude range.

Furnace must operate within the temperature rise ranges specified on the furnace rating plate. Determine the air temperature as follows:

1.Place thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not ’see’ heat exchangers so that radiant heat does not affect thermometer readings. This practice is particularly important with straight run ducts.

2.When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to determine air temperature rise.

NOTE: Temperature rise can be determined for low-fire operation by placing setup switch SW-2 on control center in ON position. For high-heat operation, place setup switch SW-2 in OFF position and jumper R-W2 on control center. DO NOT forget to return setup switch to OFF position and remove R-W2 jumper upon completion of testing. (See Fig. 31 for switch and terminal location.)

3.This furnace is capable of automatically providing proper airflow to maintain the temperature rise within the range specified on unit rating plate. If temperature rise is outside this range, proceed as follows:

a.Check gas input for low- and high-heat operation.

b.Check derate for altitude if applicable.

c.Check all return and supply ducts for excessive restrictions causing static pressure greater than 0.5-in. wc.

d.Ensure bypass humidifier switch (BPH) setup switch SW-3 on control center is in ON position when a bypass humidifier is used. (See Fig. 31 for switch location.)

e.Check Troubleshooting Guide for Variable-Speed 2-Stage Electronic Condensing Furnaces.

C. Set Thermostat Heat Anticipator

The thermostat heat anticipator must be set to match the amp draw of components in the R-W/W1 circuit. Accurate amp draw measurements can be obtained at the thermostat subbase terminals R and W.

Fig. 59 illustrates an easy method of obtaining thermostat amp draw measurements. The amp reading should be taken after blower motor has started and furnace is operating in low heat.

1.To operate furnace in low heat, turn setup switch SW-2 to ON position (See Fig. 31.) and connect ammeter leads across thermostat subbase R-W.

—56—

Page 56
Image 56
Bryant 355MAV instruction manual Altitude Derate Multiplier for U.S.A, Set Thermostat Heat Anticipator, Example

355MAV specifications

The Bryant 355MAV is a remarkable model that stands out in the HVAC (heating, ventilation, and air conditioning) industry for its efficiency, reliability, and advanced technology. This unit is specifically designed to provide homeowners with excellent comfort while maintaining energy efficiency, making it an ideal choice for residential applications.

One of the standout features of the Bryant 355MAV is its variable speed compressor. This technology allows the system to adjust its cooling output based on the current temperature needs of the home. By operating at multiple speed levels, the compressor can maintain a more consistent indoor climate while using significantly less energy than traditional single-speed systems. This capability translates to lower energy bills and enhanced comfort.

Additionally, the Bryant 355MAV integrates an advanced control system that offers precise temperature regulation. Homeowners can easily set their desired indoor conditions, and the thermostat will communicate with the system to ensure optimal performance. This smart technology not only enhances comfort but also extends the lifespan of the unit by preventing unnecessary strain during operation.

The 355MAV also features significant advancements in sound reduction technology. Designed with noise-absorbing materials and a quiet operation mode, this unit ensures that indoor comfort is maintained without the disruption of loud operational sounds. This makes it a perfect choice for residential settings, particularly in areas where noise sensitivity is a concern.

Energy efficiency is another key characteristic of the Bryant 355MAV. The unit is certified with a high Seasonal Energy Efficiency Ratio (SEER) rating, which means it meets strict energy consumption standards. This not only reflects its eco-friendliness but also contributes to significant savings on utility bills over time.

Moreover, the Bryant 355MAV uses environmentally friendly refrigerants that comply with EPA regulations, further solidifying its commitment to sustainability. This, combined with durable construction and a reliable warranty, ensures that homeowners can expect lasting performance from the system.

In conclusion, the Bryant 355MAV offers an impressive array of features, including a variable speed compressor, advanced control systems, sound reduction technology, and high energy efficiency. These characteristics make it an exceptional option for those seeking a reliable and efficient HVAC solution in their homes. With its commitment to comfort, savings, and sustainability, the Bryant 355MAV continues to be a popular choice among homeowners looking to enhance their indoor environments.