Table 4—Electrical Data
UNIT | VOLTS— | OPERATING | MAX | UNIT | MIN | MAX WIRE | MAX FUSE | ||
HERTZ— | VOLTAGE RANGE | UNIT | WIRE | LENGTH | OR CKT BKR | ||||
SIZE | AMPACITY† | ||||||||
PHASE | Max* | Min* | AMPS | SIZE | (FT)‡ | AMPS** | |||
|
| ||||||||
042040 | 127 | 104 | 8.9 | 12.0 | 14 | 31 | 15 | ||
042060 | 127 | 104 | 8.9 | 12.0 | 14 | 31 | 15 | ||
042080 | 127 | 104 | 8.9 | 12.0 | 14 | 31 | 15 | ||
060080 | 127 | 104 | 13.8 | 17.9 | 12 | 32 | 20 | ||
060100 | 127 | 104 | 13.8 | 18.1 | 12 | 32 | 20 | ||
060120 | 127 | 104 | 11.6 | 15.3 | 12 | 37 | 20 | ||
|
|
|
|
|
|
|
|
|
* Permissible limits of voltage range at which unit will operate satisfactorily.
†Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load amps.
‡ Length shown is a measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. **
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
ALUMINUM
WIRE
A93033
Fig. 28—Disconnect Switch and Furnace
CAUTION: Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. (See Fig. 28.)
WARNING: The furnace casing MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA
J-BOX RELOCATION
1.Remove 2 screws holding auxiliary
2.Rotate
CAUTION: If manual disconnect switch is to be mounted on furnace, select a location where a drill or fastener will not contact electrical or gas components.
B. 24-V Wiring
Make field
NOTE: Use AWG No. 18
NOTE: For
C.Accessories
1.Electronic Air Cleaner (EAC)
The control center EAC terminals are energized with 115v
a.Two extension leads are connected to the control center EAC terminals to assist field installation of an EAC. (See Fig. 31.) To use these leads, proceed with the following:
(1.) Strip EAC power lead insulation approximately 1/4 in.
(2.) Insert stripped end into
(3.) Strip EAC neutral lead insulation approximately 1/4 in.
(4.) Insert stripped end into