Bryant 355MAV instruction manual AtticLocation and Working Platform, A. Condensate Trap Location

Models: 355MAV

1 60
Download 60 pages 27.74 Kb
Page 13
Image 13
Fig. 10—Attic Location and Working Platform

COMBUSTION - AIR

INTAKE

Manual background VENT

5 3/4(146 mm)

A 12-IN. (305 mm) MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT / 1.5 TO 2.4 M) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE.

30(762 mm)MIN

WORK AREA

MANUAL

 

SHUTOFF

ACCESS OPENING

GAS VALVE

FOR TRAP

SEDIMENT

DRAIN

TRAP

CONDENSATE

 

 

TRAP

NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE

FURNACE AND CONDENSATE TRAP WHEN A CONDENSING

FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.

A93031

Fig. 10—Attic Location and Working Platform

Manual background CAUTION: The condensate trap MUST be installed below furnace. See Fig. 4 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.

NOTE: Combustion-air and vent pipes are restricted to a minimum length of 5 ft. (See Table 6.)

NOTE: A 12-in. minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 10 or 32.)

PROCEDURE 5—HORIZONTAL RIGHT (SUPPLY-AIR DISCHARGE) APPLICATIONS

A horizontal right furnace application is where furnace blower is located to the left of combustion and controls section of furnace, and conditioned air is discharged to the right.

Manual background CAUTION: Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in attic application or over a finished ceiling.

NOTE: In Canada, installations shall be in accordance with current NSCNGPIC Installation Codes and/or local codes.

NOTE: The auxiliary junction box (J-Box) MUST be relocated to opposite side of furnace casing. (See Fig. 11.) See Electrical Connection section for J-Box relocation.

A. Condensate Trap Location

The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 11.

To relocate condensate trap from the blower shelf to desired location, perform the following:

1.Remove 3 tubes connected to condensate trap.

2.Remove trap from blower shelf by gently pushing tabs inward and rotating trap

3.Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.

4.Install casing hole filler cap into blower shelf hole where trap was removed.

5.Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).

B. Condensate Trap Tubing

NOTE: See Fig. 11 or tube routing label on main furnace door to check for proper connections.

1.Collector Box Drain Tube:

a. Remove factory-installed plug from LOWER collector box drain tube (blue and white striped label).

—13—

Page 13
Image 13
Bryant 355MAV instruction manual AtticLocation and Working Platform, A. Condensate Trap Location, B. Condensate Trap Tubing