Table 13—Model 355MAV Orifice Size and Manifold Pressure for Correct Input (Continued)

(Tabulated Data Based on 20,000 Btuh High Heat/13,000 Btuh Low Heat per Burner, Derated 2 Percent for Each 1000 ft Above

Sea Level)

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

RANGE

HEAT VALUE

 

 

 

 

 

 

 

(FT)

(BTU/CU FT)

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

 

 

no.

 

Pressure

no.

 

Pressure

no.

 

Pressure

no.

 

Pressure

no.

 

Pressure

 

 

 

625

43

 

3.8/1.6

42

 

3.3/1.4

42

 

3.4/1.4

42

 

3.5/1.5

42

 

3.6/1.5

 

 

 

650

43

 

3.5/1.5

43

 

3.7/1.6

43

 

3.8/1.6

42

 

3.2/1.4

42

 

3.3/1.4

 

 

 

675

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.5

43

 

3.6/1.5

43

 

3.7/1.6

Only

 

7001

700

44

 

3.5/1.5

44

 

3.6/1.5

44

 

3.8/1.6

43

 

3.4/1.4

43

 

3.5/1.5

 

725

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.5

44

 

3.6/1.5

44

 

3.7/1.6

U.S.A.

 

to

 

 

 

 

 

 

750

45

 

3.7/1.6

45

 

3.8/1.6

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.5

 

8000

 

 

 

 

 

 

 

775

45

 

3.5/1.5

45

 

3.6/1.5

45

 

3.7/1.6

45

 

3.8/1.6

44

 

3.3/1.4

 

 

 

800

45

 

3.3/1.4

45

 

3.4/1.4

45

 

3.5/1.5

45

 

3.6/1.5

45

 

3.7/1.6

 

 

 

825

47

 

3.6/1.5

45

 

3.2/1.3

45

 

3.3/1.4

45

 

3.4/1.4

45

 

3.5/1.5

 

 

 

850

47

 

3.4/1.4

47

 

3.5/1.5

47

 

3.7/1.5

45

 

3.2/1.3

45

 

3.3/1.4

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

RANGE

HEAT VALUE

 

 

 

 

 

 

 

(FT)

(BTU/CU FT)

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

 

 

no.

 

Pressure

no.

 

Pressure

no.

 

Pressure

no.

 

Pressure

no.

 

Pressure

 

 

 

600

43

 

3.8/1.6

42

 

3.3/1.4

42

 

3.4/1.4

42

 

3.5/1.5

42

 

3.6/1.5

 

 

 

625

43

 

3.5/1.5

43

 

3.6/1.5

43

 

3.8/1.6

42

 

3.2/1.4

42

 

3.3/1.4

Only

 

Altitudes

650

44

 

3.7/1.6

43

 

3.4/1.4

43

 

3.5/1.5

43

 

3.6/1.5

43

 

3.7/1.6

 

675

44

 

3.5/1.5

44

 

3.6/1.5

44

 

3.7/1.6

44

 

3.8/1.6

43

 

3.4/1.5

 

8001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U.S.A.

 

700

44

 

3.2/1.4

44

 

3.3/1.4

44

 

3.4/1.5

44

 

3.6/1.5

44

 

3.7/1.6

 

to

 

 

 

 

 

 

725

45

 

3.6/1.5

45

 

3.8/1.6

44

 

3.2/1.4

44

 

3.3/1.4

44

 

3.4/1.4

 

9000

 

 

 

 

 

 

 

750

45

 

3.4/1.4

45

 

3.5/1.5

45

 

3.6/1.5

45

 

3.8/1.6

44

 

3.2/1.4

 

 

 

 

 

 

 

 

 

 

 

775

45

 

3.2/1.3

45

 

3.3/1.4

45

 

3.4/1.4

45

 

3.5/1.5

45

 

3.6/1.5

 

 

 

800

47

 

3.6/1.5

47

 

3.7/1.6

45

 

3.2/1.3

45

 

3.3/1.4

45

 

3.4/1.4

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

0.58

 

0.60

 

0.62

 

0.64

 

0.66

 

RANGE

HEAT VALUE

 

 

 

 

 

 

 

(FT)

(BTU/CU FT)

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

 

 

 

no.

 

Pressure

no.

 

Pressure

no.

 

Pressure

no.

 

Pressure

no.

 

Pressure

 

 

 

575

43

 

3.8/1.6

42

 

3.2/1.4

42

 

3.3/1.4

42

 

3.5/1.5

42

 

3.6/1.5

 

 

 

600

43

 

3.5/1.5

43

 

3.6/1.5

43

 

3.7/1.6

42

 

3.2/1.3

42

 

3.3/1.4

Only

 

 

625

44

 

3.7/1.6

44

 

3.8/1.6

43

 

3.5/1.5

43

 

3.6/1.5

43

 

3.7/1.6

 

9001

650

44

 

3.4/1.4

44

 

3.5/1.5

44

 

3.7/1.5

44

 

3.8/1.6

43

 

3.4/1.4

U.S.A.

 

to

675

44

 

3.8/1.6

44

 

3.3/1.4

44

 

3.4/1.4

44

 

3.5/1.5

44

 

3.6/1.5

 

10,000

700

45

 

3.6/1.5

45

 

3.7/1.6

45

 

3.8/1.6

44

 

3.3/1.4

44

 

3.4/1.4

 

 

725

45

 

3.3/1.4

45

 

3.4/1.5

45

 

3.6/1.5

45

 

3.7/1.6

45

 

3.8/1.6

 

 

 

 

 

 

 

 

 

 

 

750

47

 

3.7/1.6

45

 

3.2/1.4

45

 

3.3/1.4

45

 

3.4/1.5

45

 

3.5/1.5

 

 

 

775

47

 

3.5/1.5

47

 

3.6/1.5

47

 

3.7/1.6

45

 

3.2/1.4

45

 

3.3/1.4

*Orifice numbers 45 are factory installed.

CANADA

At installation altitudes from 2000 to 4500 ft, this furnace must be derated 5 percent by an authorized Gas Conversion Station or Dealer. To determine correct input rate for altitude, see example above and use 0.95 as derate multiplier factor.

b. Reinstall burner box cover.

NOTE: Clocking gas input rate MUST always be performed with the burner box cover INSTALLED.

c.Check that gas valve adjustment caps are in place for proper input to be clocked.

d.Obtain yearly heat value average for local gas supply.

NOTE: Be sure heating value of gas used for calculations is correct for your altitude. Consult local gas utility for altitude adjustment of gas heating value.

e.Check and verify orifice size in furnace. NEVER ASSUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY.

f.Turn off all other gas appliances and pilots.

g.Move setup switch SW-2 to ON position. (See Fig. 31.) This keeps furnace locked in low-heat operation.

h.Jumper R to W/W1.

i.Let furnace run for 3 minutes in low-heat operation.

j.Measure time (in sec) for gas meter to complete 1 revolution. Note reading.

k.Refer to Table 15 for cubic ft of gas per hr.

l.Multiply gas rate cu ft/hr by heating value (Btu/cu ft).