Fig. 20 — 42VE Cabinet Lowboy Unit Dimensions
A42-4114

14-3/8

(368)

LEGEND

1 — Fan Switch, 3-Speed, behind Access Door 2 — Front Panel Fastener

3 — Stamped Supply Grille

4 — Supply Conn, 5/8-in. OD

5 — Return Conn, 5/8-in. OD

6 — Stamped Return Grille

7 — Filter

8 — Air Vent, 1/8-in. MPT

9 — Optional Valve Package (inside cabinet) 10 — Drain Pan, Auxiliary, with 3/4-in. MPT

Drain Connection 11 — Return Air Grille

NOTES:

1. Right hand unit shown; left hand unit opposite. Coil connection locations are ± 5/8-in.

2. Unit sizes 02 through 04 have one motor, 2 blowers; size 06 has 2 motors, 4 blowers.

3. Cabinet has an Arctic White baked finish.

4. Height increases by 2 in. with electric heat.

5. Standard 2-row coil shown.

6. Not shown: 1/2-in. fiberglass insulation on inside of casing, closed cell foam on main drain pan.

7. For optional coil connections, view 42VC-203-1 using the Fan Coil Builder.

8. Valve package is factory-installed inside the cabinet when ordered with the unit (based on component size).

9. Dimensions shown in inches (mm).

 

NOM

 

DIMENSIONS (in.)

 

QTY/UNIT

FACE AREA

UNIT

UNIT SIZE

AIRFLOW

 

 

 

 

 

 

WEIGHT*

A

B

D

C

Blower

Motor

(sq ft)

 

(Cfm)

(lb)

 

 

 

 

 

 

 

 

02

200

41

22

33/4

17

2

1

1.18

72

03

300

46

27

4

211/2

2

1

1.53

100

04

400

54

35

35/8

301/4

2

1

2.08

108

06

600

68

49

41/16

433/8

4

2

3.06

154

*Unit weights are based on dry coils and minimum rows. Weights exclude packaging, valves, and other components.

Fig. 20 — 42VE Cabinet Lowboy Unit Dimensions

23

Page 23
Image 23