Table 5 — Piping Components
SYMBOL/SKETCH | DESCRIPTION | CV FACTOR | RATING* | STEAM | ||||
1/ in. | 3/ | 4 | in. | PSI | F | USE | ||
|
| 2 |
|
|
|
|
| |
| MANUAL AIR VENT: Threaded brass needle |
|
|
|
|
|
|
|
| valve with screwdriver slot for adjustment. |
|
|
|
|
|
|
|
| Application — Body brazed into high point of | N/A | N/A | 400 | 100 | NO | ||
| heating and cooling coils for bleeding air from | |||||||
| coil. Standard item on all hydronic coils (not |
|
|
|
|
|
|
|
| used on steam or DX coils). Should not be |
|
|
|
|
|
|
|
| used in lieu of main system air vents. |
|
|
|
|
|
|
|
| AUTOMATIC AIR VENT: Nickel plated brass |
|
|
|
|
|
|
|
| valve, |
|
|
|
|
|
|
|
| check and quick vent feature via knurled vent |
|
|
|
|
|
|
|
| screw. |
|
|
|
|
|
|
|
| Application — Optional replacement for man- |
|
|
|
|
|
|
|
| ual air vent. Automatically passes minute |
|
|
|
|
|
|
|
| quantities of air through the fiber discs which | N/A | N/A | 125 | 240 | NO | ||
| expand upon contact with water, completely | |||||||
|
|
|
|
|
|
|
| |
| sealing the valve. As air accumulates, the fiber |
|
|
|
|
|
|
|
| discs dry and shrink, repeating the cycle. Not |
|
|
|
|
|
|
|
| recommended for removing large quantities of |
|
|
|
|
|
|
|
| air encountered during initial |
|
|
|
|
|
|
|
| quent draining and refilling. Should not be |
|
|
|
|
|
|
|
| used in lieu of main system air vents. |
|
|
|
|
|
|
|
| SWAGE: Copper tube end expanded to accept |
|
|
|
|
|
|
|
| a copper tube of the same size for factory or |
|
|
|
|
|
|
|
| field brazing. | N/A | N/A | 300 | 200 | YES | ||
| Application — Used where possible for all tub- |
|
|
|
|
|
|
|
| ing joints for best joint integrity. |
|
|
|
|
|
|
|
| UNION: Combination wrought copper/cast |
|
|
|
|
|
|
|
| brass union assembly, solder by solder. |
|
|
|
|
|
|
|
| Application — Used for quick connect (and dis- | N/A | N/A | 300 | 200 | YES | ||
| connect) of valve package components to min- |
|
|
|
|
|
|
|
| imize field labor and facilitate servicing of unit. |
|
|
|
|
|
|
|
| INSERTION TEST PORT: Brass body valve |
|
|
|
|
|
|
|
| for acceptance of test probe (up to 1/ in. |
|
|
|
|
|
|
|
| 8 |
|
|
|
|
|
|
|
| diameter). |
|
|
|
|
|
|
|
| Application — Installed on one (or both) sides | N/A | N/A | 250 | 250 | NO | ||
| of the coil to allow for temperature or pressure |
|
|
|
|
|
|
|
| sensing. Used for close tolerance water bal- |
|
|
|
|
|
|
|
| ancing and service analysis. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
LEGEND
Cv — Coefficient of Velocity
DX — Direct Expansion
*Check all system component pressure ratings (coils, values, pumps, etc.) with manufacturer and any applicable local or national piping codes prior to specifying system pressure rating.
NOTES:
1.Motorized
2.Motorized
50