Thermostatic 2-Pipe Auxiliary Electric Heat with Valve Control — This system, also called twilight or intermediate season electric heat, goes a long way towards solving the spring and fall control problems of 2-pipe systems.

Chilled water can be run late into the fall, turned on early in the spring and heat will still be available to all units whenever required.

In winter the system is switched over to hot water. Two changeover devices are required for this. One device switches the action of the thermostat and the other locks out the electric heat when hot water is in the coil.

With this system, the fan runs continuously unless manually switched to OFF position. Fan must be on before thermostat can send signal to open chilled water valve or turn on electric heater.

Two control methods are available:

1.Use the standard automatic changeover thermostat with a dead band between heating and cooling.

2.Use a manual changeover thermostat. With this method only one changeover is required.

Be sure to include a 2-way or 3-way electric valve with this system.

NOTE: Wiring diagrams are for 120-v power supply. If other voltages for heaters or controls are specified, wiring may differ from that shown. See Fig. 57 and 58 for line voltage control. See Fig. 59 and 60 for 24-v control.

a42-4066

Δ120-V WHT ALL OTHERS BLK

NEC CLASS 1 WIRING

Fig. 57 — 42SG,SH,SJ,VA,VB,VC,VE,VF 2-Pipe Heating and Cooling with Auxiliary Heat —

Unit-Mounted Thermostat (Line Voltage)