Thermostatic
Chilled water can be run late into the fall, turned on early in the spring and heat will still be available to all units whenever required.
In winter the system is switched over to hot water. Two changeover devices are required for this. One device switches the action of the thermostat and the other locks out the electric heat when hot water is in the coil.
With this system, the fan runs continuously unless manually switched to OFF position. Fan must be on before thermostat can send signal to open chilled water valve or turn on electric heater.
Two control methods are available:
1.Use the standard automatic changeover thermostat with a dead band between heating and cooling.
2.Use a manual changeover thermostat. With this method only one changeover is required.
Be sure to include a
NOTE: Wiring diagrams are for
|
NEC CLASS 1 WIRING |
Fig. 57 — 42SG,SH,SJ,VA,VB,VC,VE,VF
Unit-Mounted Thermostat (Line Voltage)