Carrier 42C, 42S, 42D, 42V specifications Piping Components cont, Symbol/Sketch

Models: 42V 42D 42S 42C

1 72
Download 72 pages 52.3 Kb
Page 52
Image 52
Manual background

Table 5 — Piping Components (cont)

SYMBOL/SKETCH

DESCRIPTION

 

CV FACTOR

RATING*

STEAM

1/

2

in.

3/ in.

PSI

F

USE

 

 

 

 

 

 

4

 

 

 

 

STRAINER: Y-type body with 50 mesh stain-

 

 

 

 

 

 

 

 

less steel screen.

 

 

 

 

 

 

 

 

Application — Used for removal of small parti-

 

 

 

 

 

 

 

 

cles from system water during normal system

 

 

 

 

 

 

 

 

operation. Should not be used in lieu of main

9.0

19.0

400

250

N/A

 

system strainers. Strainer screen may have to

 

Clean

Clean

 

be removed during initial high pressure sys-

 

 

 

 

 

 

 

 

 

 

 

 

tem flushing during start-up. Screen should be

 

 

 

 

 

 

 

 

removed and cleaned per normal mainte-

 

 

 

 

 

 

 

 

nance schedule (provisions for strainer blow-

 

 

 

 

 

 

 

 

down not provided).

 

 

 

 

 

 

 

 

GATE VALVE: Manual shut-off valve.

 

 

 

 

 

 

 

 

Application — Used for unit isolation during

19.8

36.0

200

200

NO

 

system flushing, servicing, etc. Do not use for

 

 

 

 

 

 

 

 

 

water balancing.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLOBE VALVE: Standard pattern, manual

 

 

 

 

 

 

 

 

shut-off and throttling valve.

 

 

 

 

 

 

 

 

Application — Used for unit isolation. Not rec-

1.8

3.9

200

200

NO

 

ommended for high flow rates due to relatively

 

 

 

 

 

 

 

 

 

high pressure drop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPRESSION STOP VALVE:

 

 

 

 

 

 

 

 

Manual shut-off valve.

 

 

 

 

 

 

 

 

Application — Used for unit isolation during

2.3

5.4

150

200

NO

 

system flushing, servicing, etc. Not recom-

 

 

 

 

 

 

 

 

 

mended for high flow rates due to relatively

 

 

 

 

 

 

 

 

high pressure drop.

 

 

 

 

 

 

 

 

BALL VALVE: Manual balance and shut-off

 

 

 

 

 

 

 

 

valve.

 

 

 

 

 

 

 

 

Application — Used for unit isolation and

 

 

 

 

 

 

 

 

water flow balancing. Without memory stop

4.0

7.5

400

200

YES

 

feature water balance point must be marked

 

 

 

 

 

 

 

 

 

by installer (if necessary). Check specifica-

 

 

 

 

 

 

 

 

tions for service fittings required when used

 

 

 

 

 

 

 

 

for water balancing.

 

 

 

 

 

 

 

 

BALL VALVE WITH MEMORY STOP:

 

 

 

 

 

 

 

 

Manual balance and shut-off valve.

 

 

 

 

 

 

 

 

Application — Used for unit isolation and

 

 

 

 

 

 

 

 

water flow balancing. The adjustable memory

4.0

7.5

400

200

N/A

 

stop feature allows return to the balance point

 

 

 

 

 

 

 

 

 

after shut-off. Check specifications for

 

 

 

 

 

 

 

 

service fittings required when used for water

 

 

 

 

 

 

 

 

balancing.

 

 

 

 

 

 

 

LEGEND

Cv — Coefficient of Velocity

DX — Direct Expansion

*Check all system component pressure ratings (coils, values, pumps, etc.) with manufacturer and any applicable local or national piping codes prior to specifying system pressure rating.

NOTES:

1.Motorized 2-way valves have a maximum close-off differential of 25 psi.

2.Motorized 3-way valves have a maximum close-off differential of 10 psi.