Table 5 — Piping Components (cont)
SYMBOL/SKETCH | DESCRIPTION |
| CV FACTOR | RATING* | STEAM | ||||
1/ | 2 | in. | 3/ in. | PSI | F | USE | |||
|
| ||||||||
|
|
|
| 4 |
|
|
| ||
| STRAINER: |
|
|
|
|
|
|
| |
| less steel screen. |
|
|
|
|
|
|
| |
| Application — Used for removal of small parti- |
|
|
|
|
|
|
| |
| cles from system water during normal system |
|
|
|
|
|
|
| |
| operation. Should not be used in lieu of main | 9.0 | 19.0 | 400 | 250 | N/A | |||
| system strainers. Strainer screen may have to | ||||||||
| Clean | Clean | |||||||
| be removed during initial high pressure sys- |
|
|
| |||||
|
|
|
|
|
|
|
| ||
| tem flushing during |
|
|
|
|
|
|
| |
| removed and cleaned per normal mainte- |
|
|
|
|
|
|
| |
| nance schedule (provisions for strainer blow- |
|
|
|
|
|
|
| |
| down not provided). |
|
|
|
|
|
|
| |
| GATE VALVE: Manual |
|
|
|
|
|
|
| |
| Application — Used for unit isolation during | 19.8 | 36.0 | 200 | 200 | NO | |||
| system flushing, servicing, etc. Do not use for | ||||||||
|
|
|
|
|
|
|
| ||
| water balancing. |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
| GLOBE VALVE: Standard pattern, manual |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
| Application — Used for unit isolation. Not rec- | 1.8 | 3.9 | 200 | 200 | NO | |||
| ommended for high flow rates due to relatively | ||||||||
|
|
|
|
|
|
|
| ||
| high pressure drop. |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
| COMPRESSION STOP VALVE: |
|
|
|
|
|
|
| |
| Manual |
|
|
|
|
|
|
| |
| Application — Used for unit isolation during | 2.3 | 5.4 | 150 | 200 | NO | |||
| system flushing, servicing, etc. Not recom- | ||||||||
|
|
|
|
|
|
|
| ||
| mended for high flow rates due to relatively |
|
|
|
|
|
|
| |
| high pressure drop. |
|
|
|
|
|
|
| |
| BALL VALVE: Manual balance and |
|
|
|
|
|
|
| |
| valve. |
|
|
|
|
|
|
| |
| Application — Used for unit isolation and |
|
|
|
|
|
|
| |
| water flow balancing. Without memory stop | 4.0 | 7.5 | 400 | 200 | YES | |||
| feature water balance point must be marked | ||||||||
|
|
|
|
|
|
|
| ||
| by installer (if necessary). Check specifica- |
|
|
|
|
|
|
| |
| tions for service fittings required when used |
|
|
|
|
|
|
| |
| for water balancing. |
|
|
|
|
|
|
| |
| BALL VALVE WITH MEMORY STOP: |
|
|
|
|
|
|
| |
| Manual balance and |
|
|
|
|
|
|
| |
| Application — Used for unit isolation and |
|
|
|
|
|
|
| |
| water flow balancing. The adjustable memory | 4.0 | 7.5 | 400 | 200 | N/A | |||
| stop feature allows return to the balance point | ||||||||
|
|
|
|
|
|
|
| ||
| after |
|
|
|
|
|
|
| |
| service fittings required when used for water |
|
|
|
|
|
|
| |
| balancing. |
|
|
|
|
|
|
|
LEGEND
Cv — Coefficient of Velocity
DX — Direct Expansion
*Check all system component pressure ratings (coils, values, pumps, etc.) with manufacturer and any applicable local or national piping codes prior to specifying system pressure rating.
NOTES:
1.Motorized
2.Motorized
52