LEGEND
CR — Cold Water Return
CS — Cold Water Supply
D — Drain
HR — Hot Water Return
HS — Hot Water Supply
R — Return
S — Supply
ITEM | DESCRIPTION | QTY |
1 | Full Riser Chase | 1 |
2 | Electrical Knockouts | 1 |
3 | 3/5 | |
4 | Strip Heater (Optional) | 1 |
5 | Limit Switch**†† (Optional) | 1 |
6 | 2/4 | |
7 | Flexible Drain | 1 |
8 | Drain Pan | 1 |
9 | Coil | 1 |
10 | Filter, Throwaway, | 1 |
11 | Air Vent, Manual | 1 |
12 | Control Box | 1 |
13 | Cabinet Camloc® Fasteners | 2 |
14 | 1 | |
15 | Electrical Access Panel | 1 |
16 | Riser, Supply and Return (Copper) | 2/4 |
17 | Riser, Drain (Copper) | 1 |
18 | Return Air Panel | 1 |
19 | Return Air Blockoff Panel (Optional) | 1 |
20 | Motor, | 1 |
21 | Blower | 1 |
22 | Thermostat | 1 |
23 | Hinged Control Access Door | 1 |
24 | Double Deflection Steel Core Grille Assembly | 1 |
*Drawing provided for reference only. Dimensions may vary with options ordered.
NOTES:
1.Units are fabricated of
2.
3.Risers are piped to coil with valves as specified.
4.Blower, motor, valves, coil, and filter are accessible through the return air opening.
5.Unit is insulated with coated fiberglass.
6.Control box is insulated with
7.Riser length = [(floor to floor) +2 in.], maximum riser length = 115 inches.
8.Maximum riser size is
9.Expansion loops in hot water heating circuits as required.
10.A
11.Drawing is pictorial (see unit arrangements for actual supply and return air orientation).
12. 42SHA available in front return only. |
|
|
|
|
|
| ||||||
13. All dimensions are in inches. |
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
UNIT | NOM |
|
|
|
| DIMENSIONS (in.) |
|
|
| UNIT | ||
SIZE | AIRFLOW | Single Supply | Double Supply | C | D | E | F | G | WEIGHT† | |||
(cfm) | A |
| B | A | B | (lb) | ||||||
|
|
|
|
|
|
|
|
| ||||
03 | 300 | 14 |
| 8 | 14 | 6 | 17 | 223/8 | 11/2 | 221/8 | 143/4 | 202 |
04 | 400 | 14 |
| 12 | 14 | 8 | 17 | 223/8 | 11/2 | 221/8 | 143/4 | 247 |
06 | 600 | 14 |
| 12 | 14 | 8 | 20 | 253/8 | 2 | 265/8 | 173/4 | 262 |
08 | 800 | 14 |
| 16 | 14 | 10 | 20 | 253/8 | 2 | 265/8 | 173/4 | 286 |
10 | 1000 | 18 |
| 16 | 14 | 12 | 24 | 293/8 | 3 | 311/8 | 173/4 | 311 |
12 | 1200 | 18 |
| 16 | 14 | 12 | 24 | 293/8 | 3 | 311/8 | 173/4 | 336 |
†Unit weights are based on dry coils and minimum rows. Weights exclude packaging, valves, and other components.
Fig. 29 — 42SH Cabinet Dimensions
32