Carrier 42C, 42D, 42V specifications A42-4126, 42SH Cabinet Dimensions

Models: 42V 42D 42S 42C

1 72
Download 72 pages 52.3 Kb
Page 32
Image 32
A42-4126

LEGEND

CR — Cold Water Return

CS — Cold Water Supply

D — Drain

HR — Hot Water Return

HS — Hot Water Supply

R — Return

S — Supply

ITEM

DESCRIPTION

QTY

1

Full Riser Chase

1

2

Electrical Knockouts

1

3

3-in. Expansion Section

3/5

4

Strip Heater (Optional)

1

5

Limit Switch**†† (Optional)

1

6

1/2-in. Isolation Ball Valves**

2/4

7

Flexible Drain Tube/P-Trap

1

8

Drain Pan

1

9

Coil 1/2-in. OD Tube

1

10

Filter, Throwaway, 1-in.**

1

11

Air Vent, Manual

1

12

Control Box

1

13

Cabinet Camloc® Fasteners

2

14

3-Speed Switch

1

15

Electrical Access Panel

1

16

Riser, Supply and Return (Copper)

2/4

17

Riser, Drain (Copper)

1

18

Return Air Panel

1

19

Return Air Blockoff Panel (Optional)

1

20

Motor, 3-Speed, PSC

1

21

Blower

1

22

Thermostat

1

23

Hinged Control Access Door

1

24

Double Deflection Steel Core Grille Assembly

1

**Factory-Installed. ††Field-Installed.

*Drawing provided for reference only. Dimensions may vary with options ordered.

NOTES:

1.Units are fabricated of 18-gage galvanized steel with a 16-gage galvanized fan deck, painted with Arctic White.

2.3-speed switch and thermostat are unit mounted.

3.Risers are piped to coil with valves as specified.

4.Blower, motor, valves, coil, and filter are accessible through the return air opening.

5.Unit is insulated with coated fiberglass.

6.Control box is insulated with 1/2-in. insulation for unit mounted controls.

7.Riser length = [(floor to floor) +2 in.], maximum riser length = 115 inches.

8.Maximum riser size is 21/2-in. diameter. If larger sizes are required, please consult the factory.

9.Expansion loops in hot water heating circuits as required.

10.A 9-in. x 21/4-in. slot is provided in the inside back panel for coil connection penetration to permit expansion and contraction of risers. Care must be taken to position the risers so that coil connection is at center of slot.

11.Drawing is pictorial (see unit arrangements for actual supply and return air orientation).

12. 42SHA available in front return only.

 

 

 

 

 

A42-4126

13. All dimensions are in inches.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

NOM

 

 

 

 

DIMENSIONS (in.)

 

 

 

UNIT

SIZE

AIRFLOW

Single Supply

Double Supply

C

D

E

F

G

WEIGHT†

(cfm)

A

 

B

A

B

(lb)

 

 

 

 

 

 

 

 

 

03

300

14

 

8

14

6

17

223/8

11/2

221/8

143/4

202

04

400

14

 

12

14

8

17

223/8

11/2

221/8

143/4

247

06

600

14

 

12

14

8

20

253/8

2

265/8

173/4

262

08

800

14

 

16

14

10

20

253/8

2

265/8

173/4

286

10

1000

18

 

16

14

12

24

293/8

3

311/8

173/4

311

12

1200

18

 

16

14

12

24

293/8

3

311/8

173/4

336

†Unit weights are based on dry coils and minimum rows. Weights exclude packaging, valves, and other components.

Fig. 29 — 42SH Cabinet Dimensions

32

Page 32
Image 32
Carrier 42C, 42D, 42V specifications A42-4126, 42SH Cabinet Dimensions