Carrier 42D, 42C, 42S, 42V specifications LEGEND 1 — Unit-MountedControl Box Optional

Models: 42V 42D 42S 42C

1 72
Download 72 pages 52.3 Kb
Page 22
Image 22
LEGEND
A42-4113

LEGEND

1 — Unit-Mounted Control Box (Optional)

2 — Drain Pan, Auxiliary, Shipped Loose 3 — Air Vent, 1/8-in. MPT

4 — Supply Conn, 5/8-in. OD 5 — Drain, 3/4-in. MPT

6 — Return Conn, 5/8-in. OD 7 — Filter

8 — Electrical Sheath Heater Element

9 — Discharge Opening

NOTES:

1.Right hand unit shown; left hand unit opposite. Coil connection locations are ± 5/8-in.

2.Unit sizes 02 through 04 have one motor, 2 blowers; size 06 has 2 motors, 4 blowers.

3.Standard 2-row coil shown.

4.Optional unit-mounted switch box and controls, when specified, are installed on opposite side from cooling connections.

5.Height increases by 2 in. with electric heat.

6.Not shown: 3-speed fan switch, 1/2-in. fiberglass insulation on inside of casing, closed cell foam on main drain pan.

7.Units have galvanized finish.

8.For optional coil connections, view 42VC-203-1 using the Fan Coil

Builder.

9. Dimensions shown in inches (mm).

 

NOM

 

DIMENSIONS (in.)

 

QTY/UNIT

FACE AREA

UNIT

UNIT SIZE

AIRFLOW

 

 

 

 

 

 

 

A

 

B

 

C

Blower

Motor

(sq ft)

WEIGHT* (lb)

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

02

200

23

 

22

 

17

2

1

1.18

50

03

300

28

 

27

 

22

2

1

1.53

60

04

400

36

 

35

 

30

2

1

2.08

72

06

600

50

 

49

 

44

4

2

3.06

110

*Unit weights are based on dry coils and minimum rows. Weights exclude packaging, valves, and other components.