42C,D,V DRAIN CONNECTIONS — Install drain line in accordance with all applicable codes. A continuous pitch of 1 in. per 10 ft of condensate drain line run is necessary for adequate condensate drainage. Insulate the drain line to prevent sweating. Extend the drain line straight from the drain pan before making any turns. The installer must provide proper support for the drain line to prevent undue stress on the auxiliary drain pan.

Install trapped drain line in accordance with all applicable codes (see Fig. 48). A drain trap may be required by local codes and is recommended for odor control. The differential height inlet to outlet must be at least 1-in. wg greater than the total static pressure of the unit. The differential height of the outlet to the bottom of the trap must not be less than the total static pressure of the unit.

Provide a trap of at least 2-in. near the end of the drain line to prevent odors from entering the rooms.

2 IN. MIN

CONDENSATE

 

PAN STUB-OUT

TRAP

 

7/8 IN. FIELD-SUPPLIED DRAIN EXTENSION

Fig. 48 — Typical Drain Line Details

(42D Unit Shown)

42C,D,V WATER SUPPLY/RETURN CONNECTIONS — Install piping in accordance with all applicable codes. Position valves over the drain pan. Be sure valves are in proper operat- ing position and are easily accessible for adjustment. See Fig. 44-47. Refer to Fig. 49 for copper water tube and joint material pressure ratings.

If coil and valve package connections will be made with a solder joint, care should be taken to ensure that the components in the valve package are not subjected to high temperatures, which may damage seals or other materials. Many 2-position electric control valves are provided with a manual operating lever. This lever should be in the OPEN position during all soldering operations.

If coil connection is made with a union, the coil side of the union must be prevented from turning (it must be backed up) during tightening. See Fig. 44-47 for common valve packages.

CAUTION

DO NOT OVERTIGHTEN! Overtightening will distort (egg shape) the union seal surface and destroy the union.

NOTE: The project specifications for system pressure, pres- sure drop limitations, and flow rate should be checked prior to selection of specific components or the valve package size.

42C,D,V STEAM CONNECTIONS — On units with steam heating coils, the maximum steam pressure applied to the unit should never exceed 10 psig. However, when steam is used on a 4-pipe application system with 1-row and 2-row coils the maximum steam pressure should never exceed 5 psig (suitable for only low pressure steam).

Do not drain the steam mains or take-off through the coils. Drain the mains ahead of the coils through a steam trap to the return line. Overhead returns require 1 psig of pressure at the steam trap discharge for each 2 ft elevation to ensure continu- ous condensate removal.

Proper steam trap selection and installation is necessary. As a guideline in creating a steam trap locate the steam trap dis- charge at least 12 in. below the condensate return connection. This provides sufficient hydrostatic head pressure to overcome trap losses and ensure complete condensate removal.

42C,D,V DIRECT EXPANSION (DX) REFRIGERANT PIPING — Use the condensing unit manufacturer's recom- mended line sizes and requirements. Suction line must be insulated for correct operation. Use refrigerant-grade copper lines only. The unit is not applied as a heat pump.

Thermostatic expansion valve (TXV) and sensing bulb are factory-installed on units when DX coil option is chosen with distributor and TXV.

NOTE: If a hot water coil is used in the reheat position, a field- supplied freezestat must be installed to protect the coil.

TEST AND INSULATE — When all joints are complete, perform hydrostatic test for leaks. Vent all coils at this time. Check interior unit piping for signs of leakage from shipping damage or mishandling. If leaks are found, notify a Carrier representative before initiating any repairs. Release trapped air from system (refer to Make Final Preparations section).

Never pressurize any equipment beyond specific test pres- sure. Always pressure test with an inert fluid or gas, such as clear water or dry nitrogen to avoid possible damage or injury in the event of a leak or component failure during testing.

CAUTION

All water coils must be protected from freezing after initial filling with water. Even if system is drained, unit coils may still have enough water to cause damage when exposed to temperatures below freezing.

Following the hydrostatic test, insulate all piping to prevent sweating.

To ensure compliance with building codes, restore the struc- ture's original fire resistance rating by sealing all holes with material carrying the same fire rating as the structure.

49

Page 49
Image 49
Carrier 42S, 42C, 42V specifications Typical Drain Line Details 42D Unit Shown

42V, 42D, 42S, 42C specifications

Carrier has established itself as a leader in the HVAC industry by continuously innovating and refining their products. Among their offerings, the Carrier 42D, 42C, 42S, and 42V series stand out for their advanced features, efficient technologies, and user-friendly characteristics.

The Carrier 42D series is known for its robust and energy-efficient design, making it ideal for commercial applications. This series employs a high-performance scroll compressor that enhances efficiency while minimizing noise levels. Equipped with advanced controls, the 42D allows for precise temperature management, ensuring comfort in a variety of environments. Its compact design is another notable feature, allowing for easier installation in constrained spaces while still delivering excellent performance.

Similar to the 42D, the 42C series emphasizes energy efficiency, but it comes with additional features tailored for residential applications. One of the main highlights is its variable-speed compressor technology, which provides exceptional temperature control and reduces energy consumption. This series also includes enhanced filtration systems, ensuring cleaner air quality, which is particularly important for allergy sufferers. Moreover, the 42C's intelligent control systems simplify operation and allow users to customize settings according to their preferences.

The Carrier 42S series focuses on environmentally friendly refrigerants, aligning with global sustainability trends. This series utilizes R-410A refrigerant, which has a lower impact on the ozone layer compared to traditional refrigerants. In addition to its eco-friendly attributes, the 42S boasts features such as an integrated humidity control system, which modulates humidity levels effectively, improving overall indoor air quality.

Finally, the 42V series presents a versatile solution for customers looking for advanced technology and adaptability. With smart connectivity features, the 42V allows for remote monitoring and control via mobile apps, enhancing user convenience. This series is also equipped with a state-of-the-art inverter compressor, which adjusts its speed according to the heating or cooling demand, resulting in significant energy savings.

In summary, the Carrier 42D, 42C, 42S, and 42V series each offer unique features and technological advancements that cater to the diverse needs of users in both residential and commercial settings. With a focus on energy efficiency, user-friendly controls, and environmentally sustainable practices, Carrier continues to set the standard in HVAC solutions.