NEC CLASS 2 WIRING

Fig. 60 — 42C,S,V (except VG), and 42D (600-1000 cfm) 2-Pipe Heating and Cooling with

Auxiliary Heat — Remote/Wall-Mounted Debonair® Thermostat (24-v)

Thermostat 2-Pipe Total Electric Heat with Valve Con- trol — With this system, the complete heating requirement for the space is provided by the electric heater; the water system is never changed over for heating. It is therefore possible, just as with 4-pipe systems, to have heating or cooling at any time of the year.

The fan runs continuously unless it is manually switched to OFF position. Fan must be on before thermostat can send signal to open chilled water valve or turn on electric heater.

Normally, an automatic changeover thermostat with a dead band between heating and cooling is used, but a manual changeover thermostat is also suitable. A 2-way or 3-way valve must also be used so that the chilled water is off whenever the heater is on. No changeover device to sense water temperature is necessary.

NOTE: Wiring diagrams are for 120-v power supply. If other voltages for heaters or controls are specified, wiring may differ from that shown. See Fig. 61 and 62 for line voltage control. See Fig. 63 and 64 for 24-v control.