![Manual background](/images/new-backgrounds/33740/337409x1.webp)
LEGEND
1— Junction Box (remote mount)
2— Flexible Metal Conduit
3— Strip Heater High Limit
4— Electric Strip Heater Element
5—
6— Drain Conn,
7— Drip Lip (optional)
8— Supply Duct Collar,
9— Air Vent,
10— Return Conn,
11— Supply Conn,
12— Hanger Slots (4), Rubber Grommet
has
NOTES:
1.Right hand unit shown; left hand unit opposite. Coil connection locations are
2.Unit sizes 02 and 03 have one motor, one blower; sizes 04 through 08 have one motor, 2 blowers; sizes 10 and 12 have 2 motors, 4 blowers.
3.Standard
4.Overall unit dimension increases by 4 in. with optional electric heat.
5.Not shown:
6.Units have galvanized finish.
7.For optional coil connections, view
Builder.a42-4100.eps8. Dimensions shown in inches (mm).
UNIT | NOM |
|
|
| DIMENSIONS (in.) |
|
|
| QTY/UNIT | FACE | UNIT | |||
AIRFLOW |
|
|
|
|
|
|
|
|
|
| AREA | WEIGHT* | ||
SIZE | A | A’ | B | D’ | E | F | G | H | Blower | Motor | ||||
(Cfm) | (sq ft) | (lb) | ||||||||||||
|
|
|
|
|
|
|
|
|
|
| ||||
02 | 200 | 211/4 | 311/4 | 16 | 13 | 181/4 | 61/4 | 83/4 | 193/4 | 1 | 1 | 0.83 | 38 | |
03 | 300 | 251/4 | 361/4 | 20 | 14 | 221/4 | 61/4 | 83/4 | 233/4 | 1 | 1 | 1.08 | 41 | |
04 | 400 | 311/4 | 431/4 | 26 | 15 | 281/4 | 61/4 | 83/4 | 293/4 | 2 | 1 | 1.35 | 51 | |
06 | 600 | 361/4 | 431/4 | 31 | 10 | 331/4 | 71/2 | 10 | 343/4 | 2 | 1 | 1.88 | 61 | |
08 | 800 | 431/4 | 571/4 | 38 | 17 | 401/4 | 71/2 | 10 | 413/4 | 2 | 1 | 2.31 | 66 | |
10 | 1000 | 571/4 | 651/4 | 52 | 11 | 541/4 | 71/2 | 10 | 553/4 | 4 | 2 | 3.16 | 97 | |
12 | 1200 | 651/4 | 751/4 | 60 | 13 | 621/4 | 71/2 | 10 | 633/4 | 4 | 2 | 3.65 | 109 |
*Unit weights are based on dry coils and minimum rows. Weights exclude packaging, valves, and other components.
Fig. 2 — 42CA
5