Carrier 42C, 42S, 42D, 42V specifications Thermostatic Fan Control 2-PipeSystem

Models: 42V 42D 42S 42C

1 72
Download 72 pages 52.3 Kb
Page 56
Image 56
Fig. 51 — Thermostatic Fan Control

Thermostatic Fan Control, 2-Pipe Systems — The thermo- stat cycles the fan on and off from any selected speed setting to maintain selected room temperature. Controls can be wired for heating-only, cooling-only or for heating/cooling by the addi- tion of an automatic changeover device that senses water tem- perature and changes the action of the thermostat as required. See Fig. 51.

Thermostatic Fan Control, 2-Pipe System with Safety Cycle — This control is used for high humidity situations in which condensate problems can occur if fan is turned off while chilled water is still running through the coil.

The wiring provides fan cycling from HIGH to LOW on the cooling cycle and from LOW to OFF on the heating cycle. An ON-OFF toggle switch replaces the standard 3-speed fan switch. The toggle switch can be concealed to ensure that the unit runs on low speed when cooling. This action greatly reduces the chance of condensation problems that exist with other standard fan cycling controls. See Fig. 52.

NOTES:

1.Motors are thermally protected.

2.Use copper conductors only.

3.See unit nameplate for power supply. Provide disconnect means and overload protection as required.

4.Unit-mounted thermostats are not recommended for fan control because of poor temperature sensing. Fan control not available on 42VC,VE lowboy units.

Fig. 51 — Thermostatic Fan Control

(2-Pipe System)

NOTES:

1.Motors are thermally protected.

2.Use copper conductors only.

3.See unit nameplate for power supply. Provide disconnect means and overload protection as required.

Fig. 52 — Thermostatic Fan Control (2-Pipe System with Safety Cycle)

Thermostatic Electric Valve Control, 2-Pipe — A thermo- statically controlled 2-position valve provides superior control to fan cycling. With this control, the fan runs continuously un- less it is manually switched to the OFF position. The fan must be on before the valve can be opened to supply water to the coil.

This system can be used for normal 2-pipe changeover systems and can also be furnished for cooling-only or heating- only applications by omitting the changeover and specifying which application is intended. See Fig. 53 and 54 for line volt- age control. See Fig. 55 and 56 for 24-v control.

56

Page 56
Image 56
Carrier 42C, 42S, 42D, 42V specifications Thermostatic Fan Control 2-PipeSystem