Table 5 — Piping Components (cont)

SYMBOL/SKETCH

DESCRIPTION

CV FACTOR

RATING*

STEAM

1/

2

in.

3/ in.

PSI

F

USE

 

 

 

 

 

 

4

 

 

 

 

2-WAY MOTORIZED VALVE: Electric 2-position flow

 

 

 

 

 

 

 

 

control valve (open/closed). Normally closed body

 

 

 

 

 

 

 

 

with manual override lever. Installed in supply line to

 

 

 

 

 

 

 

 

unit.

 

 

 

 

 

 

 

 

Application — All standard control and valve pack-

 

 

 

 

 

 

 

 

ages are based upon normally closed valves (valve

 

 

 

 

 

 

YES

 

electrically powered open and closed by spring

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

return when electric power removed). Manual

2.3

2.3

300

200

 

PSI

 

override lever allows valve to be placed in the open

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX.

 

position for secondary (unit) flushing, constant water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

flow prior to start-up, etc. Manual override is auto-

 

 

 

 

 

 

 

 

matically disengaged when valve is electrically acti-

 

 

 

 

 

 

 

 

vated. Consult factory for normally open valve

 

 

 

 

 

 

 

 

applications.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-WAY MOTORIZED VALVE: Electric 2-position flow

5.0

5.0

 

 

 

 

control valve (closed to coil/open to bypass or open

 

SERVICE

 

 

 

 

to coil/closed to bypass). Normally closed with man-

 

 

 

 

 

ual override lever. Installed in supply line to unit.

2.8

2.8

 

 

 

 

Application — Same comments as 2-way motorized

 

 

BYPASS

 

 

 

 

valve except with manual override lever engaged the

 

 

 

 

 

 

 

 

 

 

300

200

N/A

 

valve is open to both ports and water flow will take

 

 

 

 

 

the path of least resistance through the valve pack-

 

 

 

 

 

 

 

 

age (not necessarily 100% through the coil).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODULATING VALVE (Optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Non-Spring Return, Floating Point Actuator):

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Modulating valves are designed to control the flow in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the circuit by making incremental adjustments to the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

flow path within the valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Application — To control fluid flow in fan coil units.

4.0

300

200

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On the 42DD,SG,SJ,SH commercial fan coil units,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the factory-provided modulating valve has applica-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tion restrictions. In these models, the valve packages

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

are located in the air stream, downstream of the coil.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Due to the ambient temperature limitations of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

modulating valves, the valves can be used in the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

units listed above only with a 2-pipe cooling system.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODULATING VALVE (Requires ETO [Engineer-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ing to Order])

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Spring Return): Modulating valves are designed to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

control the flow in the circuit by making incremental

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

adjustments to the flow path within the valve.

 

 

 

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Application — Same comments as non-spring return

4.0

300

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

except when powered, the actuator moves to the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

desired position, at the same time tensing the spring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

return system. When power is removed for more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

than two minutes the spring returns the actuator to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the normal position.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AQUASTAT: Water temperature sensing electrical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Application — Clips directly on nominal size 1/2 in. or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4 in. copper tubing for water temperature sensing.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Must be correctly located for proper control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation.

 

 

 

 

LEGEND

Cv — Coefficient of Velocity

DX — Direct Expansion

*Check all system component pressure ratings (coils, values, pumps, etc.) with manufacturer and any applicable local or national piping codes prior to specifying system pressure rating.

NOTES:

1.Motorized 2-way valves have a maximum close-off differential of 25 psi.

2.Motorized 3-way valves have a maximum close-off differential of 10 psi.