| NOM |
| DIMENSIONS (in. ± 1/ ) |
|
| QTY/UNIT | UNIT | ||||
UNIT | AIRFLOW |
|
|
|
| 8 |
|
|
|
| WEIGHT* |
SIZE | A | B |
| C | D | E |
| Blower | Motor | ||
(cfm) |
|
| (lb) | ||||||||
06 | 600 | 31 | 131/ | 2 | 14 | 26 | 81/ | 2 | 1 | 1 | 150 |
08 | 800 | 36 | 181/ | 2 | 20 | 31 | 8 |
| 1 | 1 | 160 |
10 | 1000 | 40 | 221/ | 2 | 24 | 35 | 8 |
| 1 | 1 | 170 |
12 | 1200 | 45 | 271/ | 2 | 28 | 40 | 81/ | 2 | 2 | 2 | 195 |
14 | 1400 | 50 | 321/ | 2 | 34 | 45 | 8 |
| 2 | 2 | 205 |
16 | 1600 | 55 | 371/ | 2 | 38 | 50 | 81/ | 2 | 2 | 2 | 215 |
18 | 1800 | 60 | 421/ | 2 | 44 | 55 | 8 |
| 2 | 2 | 230 |
20 | 2000 | 64 | 461/ | 2 | 48 | 59 | 8 |
| 2 | 2 | 235 |
*Unit weights are based on dry coils and minimum rows. Weights exclude packaging, valves, and other components.
NOTES:
1.Right hand unit shown; left hand unit opposite.
2.Coil
3.Units fabricated of galvanized steel with an Arctic White baked finish.
4.Internal parts fabricated of galvanized steel.
5.Sizes 06, 08 and 10 have one motor, one blower. Sizes 12 through 20 have 2 motors, 2 blowers.
6.Units must have drain line pitched and trapped externally.
7.Stamped supply and return grilles are not available.
8.Bottom return air is not available.
9.For optional coil connections, view
10.Fan switch and wall plate are not shown.
11.Dimensions are in inches (mm).
LEGEND
1— Junction Box
2— Return Air Grille, Hinged, Bar Type, with Filter Frame (Anodized Aluminum Only)
3— Unit Mounting Channel (2),
4— Auxiliary Drip Lip
5— Electric Strip Heater Element (optional)
6— Coil Inlet, Copper Sweat Connection
7— Coil Outlet, Copper Sweat Connection
8— Manual Air Vent
9— Filter, Throwaway
10— Bottom Access Panel
11— Drain,
12— Drain Pan Insulated with Styrofoam
13— Side Access Panel (2)
14— Supply Air Grille (Double Deflection)
A42-4124
Fig. 27 — 42DF Exposed Ceiling Unit with Supply and Return Grille and Electric Heat Dimensions