2-9
Cisco Content Delivery Engine 100/200/300/400 Hardware Installation Guide
OL-13478-03
Chapter 2 Preparing to Install the Content Delivery Engines Safety Information
provides proper grounding only for the server. You must provide additional, proper grounding for the
rack and other devices installed in it. This system is intended for connection to a Common Bonding
Network (CBN) as defined by NEBS GR-1089.
Overcurrent protection: The server is designed for an AC line voltage source with up to 20 amperes of
overcurrent protection per cord feed. If the power system for the equipment rack is installed on a branch
circuit with more than 20 amperes of protection, you must provide supplemental protection for the
server. The overall current rating of a configured server is less than 6 amperes.
If DC Power Supplies Are Installed
Connection with a DC (Direct Current) source should only be performed by trained service personnel.
The server with DC input is to be installed in a Restricted Access Location in accordance with articles
110-16, 110-17, and 110-18 of the National Electric Code, ANSI/NFPA 70. The DC source must be
electrically isolated by double or reinforced insulation from any hazardous AC source. The DC source
must be capable of providing up to 300 watts of continuous power per feed pair.
Mains DC power disconnect: You are responsible for installing a properly rated DC power disconnect
for the server system. This mains disconnect must be readily accessible, and it must be labeled as
controlling power to the server. The circuit breaker of a centralized DC power system may be used as a
disconnect device when easily accessible and should be rated no more than 10 amps.
Grounding the server: This server is intended for installation with an isolated DC return (DC-I) and is
to be installed in a Common Bonding Network (CBN) per NEBS GR-1089. To avoid the potential for an
electrical shock hazard, you must reliably connect an earth grounding conductor to the server. The earth
grounding conductor must be #14 to #10 AWG connected to the earth ground stud(s) on the rear of the
server. The safety ground conductor should be connected to the chassis stud with a Listed closed
two-hole crimp terminal having 5/8-inch pitch. The nuts on the chassis earth ground studs should be
installed with a 10 in-lb torque. The safety ground conductor provides proper grounding only for the
server. You must provide additional, proper grounding for the rack and other devices installed in it.
Overcurrent protection: Overcurrent protection circuit breakers must be provided as part of each host
equipment rack and must be incorporated in the field wiring between the DC source and the server. The
branch circuit protection shall be rated minimum 75Vdc, 10 A maximum per feed pair. If the DC power
system for the equipment rack is installed with more than 10 amperes of protection, you must provide
supplemental protection for the server. The overall current rating of a maximum configured server is 8
amperes.
Warning
This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that
the protective device is rated not greater than:
10 Amps
Statement 1005
Warning
When stranded wiring is required, use approved wiring terminations, such as closed-loop or
spade-type with upturned lugs. These terminations should be the appropriate size for the wires and
should clamp both the insulation and conductor.
Statement 1002