Chapter 3 Starting and Configuring

Functional Overview

If the environmental status is not normal, the system reports the worst-case status level. Following is a sample overvoltage warning:

Router# show environment

Warning:+3.45 V measured at +3.27 V

The show environment last command retrieves and displays the NVRAM log, which shows the reason for the last system shutdown (if the shutdown was related to voltage or temperature) and the environmental status at that time. Air temperature is measured and displayed, and the DC voltage supplied by the power supply is also displayed.

Following is sample output of the show environment last command:

Router# show environment last

chassis

inlet

previously measured at 30C/86F

chassis

outlet 1

previously measured at 28C/82F

chassis

outlet 2

previously measured at -1C/31F

chassis

outlet 3

previously measured at -1C/31F

+3.45

V

 

previously measured at +3.27

+5.15

V

 

previously measured at +5.01

+12.15

V

 

previously measured at +12.34

-11.95

V

 

previously measured at -12.41

last shutdown reason - power supply shutdown

The show environment table command displays the temperature and voltage thresholds for each temperature sensor and for each monitored status level. These thresholds are related to those listed in Table 3-1and Table 3-2. The display also lists the shutdown threshold for the system.

Following is sample output of the show environment table command for a Cisco 7401ASR router:

Router# show environment table

Sample Point

LowCritical

LowWarning

HighWarning

HighCritical

chassis

inlet

 

 

40C/104F

50C/122F

chassis

outlet 1

 

 

43C/109F

53C/127F

chassis

outlet 2

 

 

75C/167F

75C/167F

chassis

outlet 3

 

 

50C/122F

60C/140F

+3.45

V

 

+3.26

+3.34

+3.55

+3.63

+5.15

V

 

+4.86

+4.99

+5.31

+5.43

+12.15

V

 

+11.39

+11.67

+12.62

+12.91

-11.95

V

 

-9.52

-10.73

-13.16

-14.38

System shutdown for chassis outlet 1 58C/136F

System shutdown for chassis outlet 3 65C/149F

Note Temperature ranges and values are subject to change.

The show environment all command displays an extended report that includes temperature readings and voltage readings. The show environment all command also displays a report showing which power supply slots are occupied and which are empty.

Following is sample output of the show environment all command.

With AC power supply installed:

Router# show environment all

Power Supplies:

Power supply 1 is Internal AC Power Supply. Unit is on.

Power supply 2 is unmeasured.

Cisco 7401ASR Installation and Configuration Guide

3-6

OL-5419-01 B0

 

 

Page 66
Image 66
Cisco Systems 7401ASR manual Router# show environment last, Router# show environment table, Router# show environment all