Operation

Event Management

This menu item permits changing how the Liebert NXL handles Alarms, Faults and Status informa- tion. Each event can be configured for the following:

Latch (yes/no)—Event stays active in the event window, even if the fault condition has been cleared, until user acknowledges it by pressing the “Reset” button.

Audible (yes/no)—Will set Audible alarm when event occurs

Event log (yes/no)—Will display event in Event log when it occurs

NOTE

You must press “Save” for changes to take effect.

See Table 7 for a list of alarms, fault and status messages.

Figure 14 Typical Event Management Parameters

2.2.3Status Reports Menu

This menu accesses the events records.

Event Log—Up to 1024 time/date stamped events are captured in the log. The oldest record will be overwritten with a new record once the buffer reaches 1024 events.

System Status

Total Operating Hours—Total number hours the UPS has been operational

Battery Operating Time—A running total of the battery discharge time for all events since the log was last cleared

2.2.4Startup Menu

This menu is used to start the UPS and individual devices.

Manual—This will begin the UPS startup. See 2.4 - Manual Procedures for details.

Devices

Close Trap—This will start the Input filter, if installed

Close MBD/BCB—If MBD is motor operated, the Close command will Enable and energize the motor to close. If MBD is not motorized, the Close command will Enable the breaker UVR. The MBD/BCB must be closed manually. If no MBD is selected, do not display this setting.

14

Page 20
Image 20