| UPS Alarm and Status Messages | |
Table 7 | Liebert NXL alarm and status messages (continued) | |||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
| This event is for informational purposes, and |
| |
|
| informs the user that Service Code is currently | Under normal circumstances, none. | |
Service Code | running. | If this message is active, and Service Code is not | ||
Active |
| This status message is | loaded, contact your | |
|
| condition is no longer present, the alarm and any | provider. | |
|
| control activity tied to the alarm reverts to normal. |
| |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
| An equipment temperature sensor is reporting an | Press “RESET” to clear the alarm. | |
Temp Sense Fail | invalid temperature. The controls ignore | If the alarm cannot be reset, or if the alarm condition | ||
|
| temperatures from a failed sensor. | returns, contact your | |
|
|
| provider. | |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
|
| Check the Event Log by pressing “Status Reports,” | |
|
|
| “Event Log” to investigate why the UPS tried to | |
|
| An event (such as an Inverter fault) caused an | transfer to bypass and why the BPSS failed. | |
|
| attempted automatic transfer to bypass and the | If CB3 is available (as displayed on the | |
Xfer to Byp Failed | transfer failed. | Display), close CB3 to restore power to the load. | ||
The controls detect the Static Bypass Switch | Press “RESET” to attempt to clear any latched | |||
|
| |||
|
| (BPSS) failed to assume the load and the Inverter | alarms or faults. | |
|
| was off. | If conditions appear normal, attempt to restart the | |
|
|
| UPS by pressing “Startup,” “Manual Start” and | |
|
|
| follow the prompts. | |
|
|
| Contact your |