UPS Alarm and Status Messages

Table 7

Liebert NXL alarm and status messages (continued)

 

 

 

Event Message

Event Definition

Recommended Action

 

 

This event is for informational purposes, and

 

 

 

informs the user that Service Code is currently

Under normal circumstances, none.

Service Code

running.

If this message is active, and Service Code is not

Active

 

This status message is self-clearing. When the

loaded, contact your factory-authorized service

 

 

condition is no longer present, the alarm and any

provider.

 

 

control activity tied to the alarm reverts to normal.

 

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

An equipment temperature sensor is reporting an

Press “RESET” to clear the alarm.

Temp Sense Fail

invalid temperature. The controls ignore

If the alarm cannot be reset, or if the alarm condition

 

 

temperatures from a failed sensor.

returns, contact your factory-authorized service

 

 

 

provider.

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

 

Check the Event Log by pressing “Status Reports,”

 

 

 

“Event Log” to investigate why the UPS tried to

 

 

An event (such as an Inverter fault) caused an

transfer to bypass and why the BPSS failed.

 

 

attempted automatic transfer to bypass and the

If CB3 is available (as displayed on the One-Line

Xfer to Byp Failed

transfer failed.

Display), close CB3 to restore power to the load.

The controls detect the Static Bypass Switch

Press “RESET” to attempt to clear any latched

 

 

 

 

(BPSS) failed to assume the load and the Inverter

alarms or faults.

 

 

was off.

If conditions appear normal, attempt to restart the

 

 

 

UPS by pressing “Startup,” “Manual Start” and

 

 

 

follow the prompts.

 

 

 

Contact your factory-authorized service provider.

62

Page 68
Image 68
Emerson 250-400kVA manual If the alarm cannot be reset, or if the alarm condition