Operation

2.3.4Off Battery

The battery plant can be disconnected from the UPS, if required for battery maintenance, by opening the module battery disconnect (MBD) circuit breaker. In this situation the UPS module will continue to supply conditioned power to the critical load, but if input power fails the UPS system cannot supply power to the load.

! CAUTION

When the UPS system is operating with the module battery disconnect (MBD) circuit breaker(s) open, the critical load is not protected from loss of the utility source power.

Figure 27 Load on UPS, battery not available

Bypass

BFB

Input

DC Bus

 

CB1

CB2

Module Output

Battery System

MBD

2.3.5Emergency Module Off

The Local Emergency Module Off (LEMO) mode will transfer the critical load to the bypass line and remove power from all UPS module components except the controls, bypass circuit breaker and the static switch.

The Emergency Module Off control is a guarded pad next to the display touchscreen (Figure 2).

Lift the cover and press the pad. The load will be transferred to bypass, and the battery (MBD), input and output circuit breakers will be opened (tripped). Refer to 2.5 - Shutdown Procedures.

Figure 28 Emergency modules off

Bypass

BFB

Input

CB1

DC Bus

CB2

Module Output

Battery System

MBD

22

Page 28
Image 28
Emerson 250-400kVA manual Off Battery, Emergency Module Off