| UPS Alarm and Status Messages | |
Table 7 | Liebert NXL alarm and status messages (continued) | |||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
|
| The condition clears from the Active Event Window | |
|
|
| when manual transfers are enabled. | |
|
|
| A possible reason for this condition is an unstable | |
|
| This summary event means the conditions | generator. If the generator frequency is not stable, | |
|
| or not at 60 Hz, the Inverter may have difficulty | ||
|
| required to perform a manual transfer to bypass | ||
|
| maintaining synchronization with the bypass | ||
|
| are not met (Inverter must be in sync with | ||
|
| source. | ||
|
| bypass). | ||
Manual Xfer Inhibit | To check the synchronization of the Inverter to | |||
|
| This status message is | bypass, click “Transfer” and observe the | |
|
| condition is no longer present, the message and | ||
|
| synchroscope. A | ||
|
| any control activity tied to the status event reverts | ||
|
| a varying phase angle error, rather than a stable “0” | ||
|
| to normal | degree indication. | |
|
|
| ||
|
|
| If the unit is not on generator, and the bypass | |
|
|
| voltage otherwise appears normal, contact your | |
|
|
| ||
|
| The user adjustable maximum load alarm |
| |
|
| threshold was exceeded. This is a “notification | Press “SILENCE” to silence the audible alarm. | |
|
| only” type alarm, meaning the UPS takes no | ||
|
| Check the kW load % displayed for A phase. | ||
|
| action other than sounding an audible alarm | ||
|
| To check the setpoint for the alarm, press “Config,” | ||
|
| based on this setpoint. The setting allows the user | ||
|
| to monitor the load status of the UPS. | “User Settings,” “Adjustable Setpoints,” “Max Load | |
|
| Alarm.” | ||
Max Load Alarm | For example, if the current load on Phase A is | |||
Compare the setpoint to the displayed load | ||||
Ph A |
| 50%, the user can set this setpoint to 80% and an | ||
|
| alarm is received if the added load exceeds 80%. | percentage. If the load percentage displayed is | |
|
| correct and the value exceeds the setpoint, raise | ||
|
| The alarm may also be configured with a delay, to | the setpoint to clear the alarm, or reduce the load | |
|
| prevent nuisance alarms due to cycling loads. | below the setpoint. | |
|
| The alarm is | ||
|
| Contact your | ||
|
| decreases to less than 95% of the level setting, | ||
|
|
| ||
|
| the alarm clears. |
| |
|
|
|
| |
|
| The user adjustable maximum load alarm |
| |
|
| threshold was exceeded. This is a “notification | Press “SILENCE” to silence the audible alarm. | |
|
| only” type alarm, meaning the UPS takes no | ||
|
| Check the kW load % displayed for B phase. | ||
|
| action other than sounding an audible alarm | ||
|
| To check the setpoint for the alarm, press “Config,” | ||
|
| based on this setpoint. The setting allows the user | ||
|
| “User Settings,” “Adjustable Setpoints,” “Max Load | ||
|
| to monitor the load status of the UPS. | Alarm.” | |
Max Load |
| For example, if the current load on Phase B is | ||
| Compare the setpoint to the displayed load | |||
Alarm Ph B |
| 50%, the user can set this setpoint to 80% and an | ||
| percentage. If the load percentage displayed is | |||
|
| alarm is received if the added load exceeds 80%. | correct and the value exceeds the setpoint, raise | |
|
| The alarm may also be configured with a delay, to | the setpoint to clear the alarm, or reduce the load | |
|
| prevent nuisance alarms due to cycling loads. | ||
|
| below the setpoint. | ||
|
| The alarm is | ||
|
| Contact your | ||
|
| decreases to less than 95% of the level setting, | ||
|
|
| ||
|
| the alarm clears. |
| |
|
|
|
| |
|
| The user adjustable maximum load alarm |
| |
|
| threshold was exceeded. This is a “notification | Press “SILENCE” to silence the audible alarm. | |
|
| only” type alarm, meaning the UPS takes no | ||
|
| Check the kW load % displayed for C phase. | ||
|
| action other than sounding an audible alarm | ||
|
| To check the setpoint for the alarm, press “Config,” | ||
|
| based on this setpoint. The setting allows the user | ||
|
| “User Settings,” “Adjustable Setpoints,” “Max Load | ||
|
| to monitor the load status of the UPS. | Alarm.” | |
Max Load |
| For example, if the current load on Phase C is | ||
| Compare the setpoint to the displayed load | |||
Alarm Ph C |
| 50%, the user can set this setpoint to 80% and an | ||
| percentage. If the load percentage displayed is | |||
|
| alarm is received if the added load exceeds 80%. | correct and the value exceeds the setpoint, raise | |
|
| The alarm may also be configured with a delay, to | ||
|
| the setpoint to clear the alarm, or reduce the load | ||
|
| prevent nuisance alarms due to cycling loads. | below the setpoint. | |
|
| The alarm is | ||
|
| Contact your | ||
|
| decreases to less than 95% of the level setting, | ||
|
|
| ||
|
| the alarm clears. |
| |
|
|
|
| |
|
| The Module battery disconnect is open. | Press “SILENCE” to silence the audible alarm. | |
|
| Check the status of Module Battery Disconnect | ||
MBD Open |
| This alarm is | ||
| (MBD). If it is open, the alarm is normal. | |||
| no longer present, the alarm and any control | |||
|
| If the Module Battery Disconnect is closed, contact | ||
|
| activity tied to the alarm reverts to normal. | ||
|
| your | ||
|
|
| ||
|
|
|
|
58