UPS Alarm and Status Messages

Table 7

Liebert NXL alarm and status messages (continued)

 

 

 

Event Message

Event Definition

Recommended Action

 

 

 

The condition clears from the Active Event Window

 

 

 

when manual transfers are enabled.

 

 

 

A possible reason for this condition is an unstable

 

 

This summary event means the conditions

generator. If the generator frequency is not stable,

 

 

or not at 60 Hz, the Inverter may have difficulty

 

 

required to perform a manual transfer to bypass

 

 

maintaining synchronization with the bypass

 

 

are not met (Inverter must be in sync with

 

 

source.

 

 

bypass).

Manual Xfer Inhibit

To check the synchronization of the Inverter to

 

 

This status message is self-clearing. When the

bypass, click “Transfer” and observe the

 

 

condition is no longer present, the message and

 

 

synchroscope. A non-sync condition is indicated by

 

 

any control activity tied to the status event reverts

 

 

a varying phase angle error, rather than a stable “0”

 

 

to normal

degree indication.

 

 

 

 

 

 

If the unit is not on generator, and the bypass

 

 

 

voltage otherwise appears normal, contact your

 

 

 

factory-authorized service provider.

 

 

The user adjustable maximum load alarm

 

 

 

threshold was exceeded. This is a “notification

Press “SILENCE” to silence the audible alarm.

 

 

only” type alarm, meaning the UPS takes no

 

 

Check the kW load % displayed for A phase.

 

 

action other than sounding an audible alarm

 

 

To check the setpoint for the alarm, press “Config,”

 

 

based on this setpoint. The setting allows the user

 

 

to monitor the load status of the UPS.

“User Settings,” “Adjustable Setpoints,” “Max Load

 

 

Alarm.”

Max Load Alarm

For example, if the current load on Phase A is

Compare the setpoint to the displayed load

Ph A

 

50%, the user can set this setpoint to 80% and an

 

 

alarm is received if the added load exceeds 80%.

percentage. If the load percentage displayed is

 

 

correct and the value exceeds the setpoint, raise

 

 

The alarm may also be configured with a delay, to

the setpoint to clear the alarm, or reduce the load

 

 

prevent nuisance alarms due to cycling loads.

below the setpoint.

 

 

The alarm is self-clearing. Once the load level

 

 

Contact your factory-authorized service provider.

 

 

decreases to less than 95% of the level setting,

 

 

 

 

 

the alarm clears.

 

 

 

 

 

 

 

The user adjustable maximum load alarm

 

 

 

threshold was exceeded. This is a “notification

Press “SILENCE” to silence the audible alarm.

 

 

only” type alarm, meaning the UPS takes no

 

 

Check the kW load % displayed for B phase.

 

 

action other than sounding an audible alarm

 

 

To check the setpoint for the alarm, press “Config,”

 

 

based on this setpoint. The setting allows the user

 

 

“User Settings,” “Adjustable Setpoints,” “Max Load

 

 

to monitor the load status of the UPS.

Alarm.”

Max Load

 

For example, if the current load on Phase B is

 

Compare the setpoint to the displayed load

Alarm Ph B

 

50%, the user can set this setpoint to 80% and an

 

percentage. If the load percentage displayed is

 

 

alarm is received if the added load exceeds 80%.

correct and the value exceeds the setpoint, raise

 

 

The alarm may also be configured with a delay, to

the setpoint to clear the alarm, or reduce the load

 

 

prevent nuisance alarms due to cycling loads.

 

 

below the setpoint.

 

 

The alarm is self-clearing. Once the load level

 

 

Contact your factory-authorized service provider.

 

 

decreases to less than 95% of the level setting,

 

 

 

 

 

the alarm clears.

 

 

 

 

 

 

 

The user adjustable maximum load alarm

 

 

 

threshold was exceeded. This is a “notification

Press “SILENCE” to silence the audible alarm.

 

 

only” type alarm, meaning the UPS takes no

 

 

Check the kW load % displayed for C phase.

 

 

action other than sounding an audible alarm

 

 

To check the setpoint for the alarm, press “Config,”

 

 

based on this setpoint. The setting allows the user

 

 

“User Settings,” “Adjustable Setpoints,” “Max Load

 

 

to monitor the load status of the UPS.

Alarm.”

Max Load

 

For example, if the current load on Phase C is

 

Compare the setpoint to the displayed load

Alarm Ph C

 

50%, the user can set this setpoint to 80% and an

 

percentage. If the load percentage displayed is

 

 

alarm is received if the added load exceeds 80%.

correct and the value exceeds the setpoint, raise

 

 

The alarm may also be configured with a delay, to

 

 

the setpoint to clear the alarm, or reduce the load

 

 

prevent nuisance alarms due to cycling loads.

below the setpoint.

 

 

The alarm is self-clearing. Once the load level

 

 

Contact your factory-authorized service provider.

 

 

decreases to less than 95% of the level setting,

 

 

 

 

 

the alarm clears.

 

 

 

 

 

 

 

The Module battery disconnect is open.

Press “SILENCE” to silence the audible alarm.

 

 

Check the status of Module Battery Disconnect

MBD Open

 

This alarm is self-clearing. When the condition is

 

(MBD). If it is open, the alarm is normal.

 

no longer present, the alarm and any control

 

 

If the Module Battery Disconnect is closed, contact

 

 

activity tied to the alarm reverts to normal.

 

 

your factory-authorized service provider.

 

 

 

 

 

 

 

58

Page 64
Image 64
Emerson 250-400kVA When manual transfers are enabled