UPS Alarm and Status Messages

 

 

 

 

Table 7

Liebert NXL alarm and status messages (continued)

 

 

 

Event Message

Event Definition

Recommended Action

 

 

 

Press “SILENCE” to silence the audible alarm.

Multiple Fan Fail

This summary event is active when more than

Press “RESET” to clear the alarm.

one fan has failed.

If the alarm will not clear, contact your factory-

 

 

 

 

 

authorized service provider.

 

 

 

 

 

 

The UPS input source is generator.

 

 

 

An external signal is being used to inform the

 

 

 

UPS when the power source is generator rather

Under normal conditions, no user action is required.

On Gen Active

than utility, and the signal is active.

If the UPS is not actually on generator and this

This status message is self-clearing. When the

message is active, contact your factory-authorized

 

 

 

 

condition is no longer present, the message and

service provider.

 

 

any control activity tied to the status event reverts

 

 

 

to normal.

 

 

 

The difference between the inlet air temperature

Press “SILENCE” to silence the audible alarm.

 

 

and the outlet air temperature is too great.

 

 

Check the Inlet Air Temperature on the One-Line

 

 

This alarm means excessive heat is being

 

 

Display and verify the reading is accurate, i.e. is the

 

 

generated internally resulting in a higher than

 

 

room temperature warmer than normal?

 

 

normal exhaust air temperature.

Outlet Ovtemp

If the room temperature is warmer than normal,

If the Bypass is within limits, the UPS reacts to

Limit

 

investigate and resolve the issue.

 

this alarm by transferring to Bypass and shutting

 

 

If the room temperature is normal, and the Inlet Air

 

 

off the Inverter.

 

 

Temp reading on the One-Line Display is higher

 

 

This alarm is self-clearing. When the condition is

 

 

than normal, contact your factory-authorized service

 

 

no longer present, the alarm and any control

 

 

provider.

 

 

activity tied to the alarm reverts to normal.

 

 

 

 

 

 

 

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

 

Check the Active Event Window and investigate

 

 

 

other events to further analyze.

 

 

 

Press “RESET” to attempt to reset any latched

 

 

 

events.

 

 

 

Check the One-Line Display to determine the

 

 

 

system status (on UPS, Bypass, or Off).

 

 

This summary event occurs when the detected

Check the input and bypass (dual input only) and

 

 

system output exceeds acceptable limits in either

observe the One-Line color. Green indicates good

 

 

voltage or frequency.

power present, orange means power is present but

 

 

If the UPS was on Inverter at the time of the

outside nominal range, and gray means power is

Output Fault

 

event, the UPS transfers to bypass provided the

not present.

 

 

bypass voltage is available.

If the load is off and the input voltage is ok, attempt

 

 

If the UPS was on bypass at the time of the event,

to restart the UPS by pressing “Startup,” “Manual

 

 

the UPS shuts down rather than allowing

Start,” and follow the prompts.

 

 

unacceptable voltage to reach the load.

If the Input Meter indicates input or bypass is not

 

 

 

available, investigate and resolve the power

 

 

 

problem.

 

 

 

If the load is on bypass and all alarms are reset,

 

 

 

press “Transfer,” “UPS,” to attempt to transfer back

 

 

 

to Inverter.

 

 

 

If the issue cannot be resolved, contact your

 

 

 

factory-authorized service provider.