| UPS Alarm and Status Messages | |
|
|
|
| |
Table 7 | Liebert NXL alarm and status messages (continued) | |||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
|
| Press “SILENCE” to silence the audible alarm. | |
Multiple Fan Fail | This summary event is active when more than | Press “RESET” to clear the alarm. | ||
one fan has failed. | If the alarm will not clear, contact your factory- | |||
|
| |||
|
|
| authorized service provider. | |
|
|
|
| |
|
| The UPS input source is generator. |
| |
|
| An external signal is being used to inform the |
| |
|
| UPS when the power source is generator rather | Under normal conditions, no user action is required. | |
On Gen Active | than utility, and the signal is active. | If the UPS is not actually on generator and this | ||
This status message is | message is active, contact your | |||
|
| |||
|
| condition is no longer present, the message and | service provider. | |
|
| any control activity tied to the status event reverts |
| |
|
| to normal. |
| |
|
| The difference between the inlet air temperature | Press “SILENCE” to silence the audible alarm. | |
|
| and the outlet air temperature is too great. | ||
|
| Check the Inlet Air Temperature on the | ||
|
| This alarm means excessive heat is being | ||
|
| Display and verify the reading is accurate, i.e. is the | ||
|
| generated internally resulting in a higher than | ||
|
| room temperature warmer than normal? | ||
|
| normal exhaust air temperature. | ||
Outlet Ovtemp | If the room temperature is warmer than normal, | |||
If the Bypass is within limits, the UPS reacts to | ||||
Limit |
| investigate and resolve the issue. | ||
| this alarm by transferring to Bypass and shutting | |||
|
| If the room temperature is normal, and the Inlet Air | ||
|
| off the Inverter. | ||
|
| Temp reading on the | ||
|
| This alarm is | ||
|
| than normal, contact your | ||
|
| no longer present, the alarm and any control | ||
|
| provider. | ||
|
| activity tied to the alarm reverts to normal. | ||
|
|
| ||
|
|
|
| |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
|
| Check the Active Event Window and investigate | |
|
|
| other events to further analyze. | |
|
|
| Press “RESET” to attempt to reset any latched | |
|
|
| events. | |
|
|
| Check the | |
|
|
| system status (on UPS, Bypass, or Off). | |
|
| This summary event occurs when the detected | Check the input and bypass (dual input only) and | |
|
| system output exceeds acceptable limits in either | observe the | |
|
| voltage or frequency. | power present, orange means power is present but | |
|
| If the UPS was on Inverter at the time of the | outside nominal range, and gray means power is | |
Output Fault |
| event, the UPS transfers to bypass provided the | not present. | |
|
| bypass voltage is available. | If the load is off and the input voltage is ok, attempt | |
|
| If the UPS was on bypass at the time of the event, | to restart the UPS by pressing “Startup,” “Manual | |
|
| the UPS shuts down rather than allowing | Start,” and follow the prompts. | |
|
| unacceptable voltage to reach the load. | If the Input Meter indicates input or bypass is not | |
|
|
| available, investigate and resolve the power | |
|
|
| problem. | |
|
|
| If the load is on bypass and all alarms are reset, | |
|
|
| press “Transfer,” “UPS,” to attempt to transfer back | |
|
|
| to Inverter. | |
|
|
| If the issue cannot be resolved, contact your | |
|
|
|
59