UPS Alarm and Status Messages

Table 7

Liebert NXL alarm and status messages (continued)

 

 

 

Event Message

Event Definition

Recommended Action

 

 

The UPS has re-transferred too many times and

 

 

 

is now locked on bypass.

 

 

 

The UPS attempts to perform an automatic

 

 

 

transfer back to Inverter, if the reason for the

 

 

 

transfer to bypass is determined by the controls to

 

 

 

be automatically recoverable; for example, a

Press “SILENCE” to silence the audible alarm.

 

 

temporary overload.

 

 

The number of times the UPS attempts to recover

Press “RESET” to clear any active faults or alarms.

 

 

from an automatic transfer to bypass is limited.

Provided there are no alarms or faults still present

Excess Auto

 

When the number of transfers exceeds the

that could prevent a transfer, press “Transfer,”

Rexfers

 

number allowable (default is 5 transfers per hour),

“UPS,” to transfer back to Inverter.

 

 

the UPS remains on bypass, and display this

If the transfer is successful, press “RESET” to clear

 

 

message.

the alarm. Otherwise, contact your factory-

 

 

An example of a condition that could cause this

authorized service provider.

 

 

alarm is cycling load to the UPS where the peak

 

 

 

load exceeds the overload settings. The UPS

 

 

 

transfers on the overload, re-transfers to Inverter,

 

 

 

then the overload returns. Once this occurs 5

 

 

 

times within one hour, the user must manually

 

 

 

transfer the UPS back online.

 

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

 

Check the Module Output Meter and verify the

 

 

 

output currents are normal, the kVA/kW

 

 

 

percentages are less than 100%, and the Rexfer

 

 

When the controls detect a high amplitude, short

Timeout is 00:00.

 

 

duration overload condition on the output, the

Verify the Inverter box on the One-Line Display is

 

 

static switch is turned on momentarily in parallel

green.

 

 

with the Inverter to attempt to clear the condition.

Investigate any other active alarms or faults before

Excess Paralleling

If the fault clears, the controls turn off the static

attempting to clear this fault.

 

 

switch and the load remains on Inverter. This fault

Press “RESET” to clear the fault.

 

 

condition indicates the UPS pulse paralleled too

If the Event Window is clear, press “Transfer,”

 

 

many times and is now locked on bypass (auto re-

“UPS” to transfer the load back to Inverter.

 

 

transfers to Inverter are inhibited).

If the “UPS” button is grayed out, or pressing the

 

 

 

“UPS” button does not transfer the unit back to

 

 

 

Inverter, or if the UPS immediately transfers back to

 

 

 

bypass, contact your factory-authorized service

 

 

 

provider.

 

 

This is a summary event that indicates a fuse has

Press “SILENCE” to silence the audible alarm.

 

 

opened. There are several fuses that can cause

 

 

this fault.

Check the One-Line Display and other indicators to

Fuse Fail

 

The Fuse Failure event is caused by one or more

determine the state of the unit and take appropriate

 

 

fuses reporting a failed status. The UPS may or

action.

 

 

may not transfer to bypass as a result of the failed

Contact your factory-authorized service provider.

 

 

fuse.

 

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

 

Check the Inlet Air Temperature on the One-Line

 

 

 

Display and verify the reading is accurate, i.e. is the

 

 

The air flowing into the UPS is too warm.

room temperature warmer than normal?

Inlet Ovtemp

This alarm is self-clearing. When the condition is

If the room temperature is warmer than normal,

no longer present, the alarm and any control

investigate and resolve the issue.

 

 

 

 

activity tied to the alarm reverts to normal.

If the room temperature is normal, and the Inlet Air

 

 

 

Temp reading on the One-Line Display is higher

 

 

 

than normal, contact your factory-authorized service

 

 

 

provider.

52

Page 58
Image 58
Emerson 250-400kVA manual UPS, to transfer back to Inverter