UPS Alarm and Status Messages

 

 

 

 

Table 7

Liebert NXL alarm and status messages (continued)

 

 

 

Event Message

Event Definition

Recommended Action

 

 

The correct input phase rotation should be

 

 

 

clockwise, or A-B-C. This alarm indicates the

 

 

 

sensed input phase rotation is counter-clockwise.

Press “SILENCE” to silence the audible alarm.

 

 

If this alarm occurs on an operational unit, it

Inp Phase Rotation

typically indicates upstream work was performed

Verify correct phase rotation at the input.

(input side) and the input wiring was connected

If the phase rotation is correct, contact your factory-

 

 

incorrectly.

authorized service provider.

 

 

This alarm is self-clearing. When the condition is

 

 

 

no longer present, the alarm and any control

 

 

 

activity tied to the alarm reverts to normal.

 

 

 

The displayed text for this alarm is dependent on

 

 

 

settings.

 

 

 

In response to this alarm, the user may see 1 of 4

 

 

 

possible messages:

 

 

 

1. No message but the help icon (lowercase “i“)

 

 

 

is present;

 

 

 

2. A custom message programmed by the user;

 

 

 

3. “Input Contact XY” if the contact is

 

 

 

unconfigured;

 

 

 

4. “Reduced Rect ILimit” if the contact is

 

 

 

programmed as Pre-assigned.

 

 

 

If this event is active, an external signal is wired

 

 

 

into Channel Y of Input Contact Isolator #X.

Check the wires landed on Input Contact

 

 

If the display shows Case 1 above (blank

Input Contact XY

message), it means the contact channel is set to

Isolator #X.

default but the default message was erased.

If the signal is not active, or no wires are present,

 

 

 

 

If the display shows Case 2, the user-

contact your factory-authorized service provider.

 

 

programmed event is active and the displayed

 

 

 

text is customer defined.

 

 

 

If the display shows Case 3, the contact is active

 

 

 

but was not pre-programmed (default condition).

 

 

 

If the display shows Case 4, the controls force the

 

 

 

Rectifier into Reduced Input Current Limit

 

 

 

operation (this limits the amount of current

 

 

 

available to charge the battery - typically during

 

 

 

generator operation).

 

 

 

This alarm message is self-clearing. When the

 

 

 

condition is no longer present, the message and

 

 

 

any control activity tied to the alarm will revert to

 

 

 

normal.

 

Input Contact

Input Contact Interface #1 has failed to

 

Interface #1

 

 

Communication

communicate in a timely fashon.

 

Failure

 

 

 

Input Contact

Input Contact Interface #2 has failed to

 

Interface #2

 

 

Communication

communicate in a timely fashon.

 

Failure

 

 

 

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

 

Press “RESET” to attempt to clear the alarm

 

 

 

condition.

 

 

The detected input currents are not balanced.

If the alarm clears, press “Startup,” “Device

 

 

This latching alarm indicates a potential problem

Control,” “Close Trap” to manually close the filter

Input Current

in the input filter. The controls automatically open

contactor.

Imbal

 

the filter contactor in response to this condition.

If the contactor remains closed, check the Input

 

 

The filter contactor must be manually closed once

Meter and verify the input currents are balanced.

 

 

it opens in response to this alarm.

If the contactor re-opens and the “Input Current

 

 

 

Imbalance” returns, silence the alarm, leave the

 

 

 

filter contactor open, and contact your factory-

 

 

 

authorized service provider.

53

Page 59
Image 59
Emerson 250-400kVA manual If this alarm occurs on an operational unit, it