UPS Alarm and Status Messages
APPENDIX A - UPS ALARM AND STATUS MESSAGES
Table 7 shows alarm and status messages as they appear in Liebert NXL’s touchscreen and in the history log, along with a description and recommended actions, if any.
If the recommended action fails to correct the condition, contact your
The “Service Telephone Number” can be found by pressing “CONFIG,” “Ratings,” “More>>” on the menu bar.
Table 7 | Liebert NXL alarm and status messages |
| ||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
|
|
| |
|
| An Automatic Restart was enabled but has failed |
| |
|
| to complete. |
| |
|
| With Automatic Restart enabled, the unit | Press “SILENCE” to silence the audible alarm. | |
|
| automatically restarts after an End of Discharge | ||
|
| (EOD) event. This alarm means that one of the | Check the active events to determine the status of | |
|
| auto restart requirements was true, but failed | the UPS. | |
|
| before the restart sequence completed. | If “Auto Restart Fail” is the only alarm present, | |
Auto Restart Fail | For example, one conditional requirement for | attempt a manual start of the unit by pressing | ||
Automatic Restart to occur is that the Rectifier | “Startup,” “Manual Start,” then following the prompts | |||
|
| |||
|
| Input Voltage must be within acceptable limits. If, | to attempt to place the unit back online. | |
|
| during the restart sequence, the input voltage | If the manual start fails, or if there are other alarms | |
|
| drops out of tolerance, the Automatic Restart will | present that won’t clear, contact your factory- | |
|
| fail. | authorized service provider. | |
|
| This alarm is |
| |
|
| no longer present, the alarm and any control |
| |
|
| activity tied to the alarm reverts to normal. |
| |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
|
| Press “RESET” to attempt to clear active events. | |
|
| The condition that caused an automatic transfer | This does not clear the “Auto Retransfer Failed” | |
|
| alarm. | ||
|
| to bypass failed to clear within a specified time | ||
|
| If all other alarm conditions clear, attempt a manual | ||
|
| delay. | ||
|
| transfer back to Inverter by pressing “Transfer,” | ||
Auto Rexfer Failed | An example of a recoverable transfer (one which | |||
“UPS.” | ||||
|
| the controls may attempt to recover from | ||
|
| If the transfer is successful, press “RESET” to clear | ||
|
| automatically) is an overload that exceeded the | ||
|
| this alarm from the Active Event Window. If the UPS | ||
|
| overload time curve. | ||
|
| fails to transfer and the active messages do not | ||
|
|
| ||
|
|
| explain the reason, contact your | |
|
|
| service provider. | |
|
| Battery Circuit Breaker “#” is open. | Press “SILENCE” to silence the audible alarm. | |
|
| This status message is | ||
|
| Check the status of Battery Circuit Breaker “#”. If it | ||
|
| condition is no longer present, the message and | ||
Batt CB “#” Open | is open, the alarm is normal. | |||
any control activity tied to the status event reverts | ||||
|
| If Battery Circuit Breaker “#” is closed, contact your | ||
|
| to normal. (The Liebert NXL has eight battery | ||
|
| circuit breakers.) | ||
|
|
|
43