UPS Alarm and Status Messages

APPENDIX A - UPS ALARM AND STATUS MESSAGES

Table 7 shows alarm and status messages as they appear in Liebert NXL’s touchscreen and in the history log, along with a description and recommended actions, if any.

If the recommended action fails to correct the condition, contact your factory-authorized service pro- vider.

The “Service Telephone Number” can be found by pressing “CONFIG,” “Ratings,” “More>>” on the menu bar.

Table 7

Liebert NXL alarm and status messages

 

 

 

 

Event Message

Event Definition

Recommended Action

 

 

 

 

 

 

An Automatic Restart was enabled but has failed

 

 

 

to complete.

 

 

 

With Automatic Restart enabled, the unit

Press “SILENCE” to silence the audible alarm.

 

 

automatically restarts after an End of Discharge

 

 

(EOD) event. This alarm means that one of the

Check the active events to determine the status of

 

 

auto restart requirements was true, but failed

the UPS.

 

 

before the restart sequence completed.

If “Auto Restart Fail” is the only alarm present,

Auto Restart Fail

For example, one conditional requirement for

attempt a manual start of the unit by pressing

Automatic Restart to occur is that the Rectifier

“Startup,” “Manual Start,” then following the prompts

 

 

 

 

Input Voltage must be within acceptable limits. If,

to attempt to place the unit back online.

 

 

during the restart sequence, the input voltage

If the manual start fails, or if there are other alarms

 

 

drops out of tolerance, the Automatic Restart will

present that won’t clear, contact your factory-

 

 

fail.

authorized service provider.

 

 

This alarm is self-clearing. When the condition is

 

 

 

no longer present, the alarm and any control

 

 

 

activity tied to the alarm reverts to normal.

 

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

 

Press “RESET” to attempt to clear active events.

 

 

The condition that caused an automatic transfer

This does not clear the “Auto Retransfer Failed”

 

 

alarm.

 

 

to bypass failed to clear within a specified time

 

 

If all other alarm conditions clear, attempt a manual

 

 

delay.

 

 

transfer back to Inverter by pressing “Transfer,”

Auto Rexfer Failed

An example of a recoverable transfer (one which

“UPS.”

 

 

the controls may attempt to recover from

 

 

If the transfer is successful, press “RESET” to clear

 

 

automatically) is an overload that exceeded the

 

 

this alarm from the Active Event Window. If the UPS

 

 

overload time curve.

 

 

fails to transfer and the active messages do not

 

 

 

 

 

 

explain the reason, contact your factory-authorized

 

 

 

service provider.

 

 

Battery Circuit Breaker “#” is open.

Press “SILENCE” to silence the audible alarm.

 

 

This status message is self-clearing. When the

 

 

Check the status of Battery Circuit Breaker “#”. If it

 

 

condition is no longer present, the message and

Batt CB “#” Open

is open, the alarm is normal.

any control activity tied to the status event reverts

 

 

If Battery Circuit Breaker “#” is closed, contact your

 

 

to normal. (The Liebert NXL has eight battery

factory-authorized service provider.

 

 

circuit breakers.)

 

 

 