SPECIFICATIONS

Table 6

Electrical specifications

 

 

 

 

 

 

 

 

 

 

 

Liebert NXL Model Size

250

 

300

 

400

 

 

 

 

 

 

Input Parameters

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Voltage to Rectifier, VAC

 

480V 3-phase, 3-wire

 

 

 

 

 

 

 

Input Voltage to Bypass, VAC

 

480V 3-phase, 3- or 4-wire

 

 

 

 

 

 

 

 

Permissible Input Voltage Range, VAC

 

 

70% to 110%

 

 

 

 

 

 

 

 

Input Frequency, Hz

 

60

 

 

 

 

 

 

 

 

 

Permissible Input Frequency Range, Hz

 

 

55 to 65

 

 

 

 

 

Input THDi at nominal voltage at full load, %

<10% with 6-pulse and passive filter

 

 

 

 

 

 

 

Input Power Factor at nominal voltage

 

>= 0.92

 

 

 

 

 

 

Flexi Power Walk-In, sec

3 to 30 (selectable) in 1 sec. Increments

 

 

 

 

 

 

Battery & DC Parameters

 

 

 

 

 

 

 

 

 

 

 

Battery Type

VRLA (Valve Regulated Lead Acid) or FLA

 

 

(Flooded Lead Acid)

 

 

 

 

 

 

Nominal Battery Bus, VDC

 

 

480V

 

 

 

 

 

 

 

 

Battery Float Voltage, VDC

 

 

540V

 

 

 

 

 

 

 

End-Cell Voltage, VDC

 

384 (for VRLA / FLA)

 

 

 

 

 

 

 

DC Ripple Voltage in float & Const V Ch.mode, %

 

<1 (RMS value) < 3.4% Vpp

 

 

 

 

 

 

 

Temperature Compensated Battery Charging

 

Standard (with temperature probe)

 

 

 

 

 

 

 

Output Parameters

 

 

 

 

 

 

 

 

 

 

 

Inverter Type

IGBT-based Sine-Sine PWM Controlled

 

 

 

 

 

 

 

Output Power, kW

225

 

270

 

360

 

 

 

 

 

 

 

 

Output Voltage

 

 

480VAC, 3-ph, 4-w

 

 

 

 

 

 

 

Output Voltage Regulation, %

 

< 1% (3-phase RMS average)

 

 

 

 

 

 

 

Output Voltage Regulation (100% Unb. Load)

 

< 2% (3-phase RMS average)

 

 

 

 

 

 

 

 

Output Frequency, Hz

 

60

 

 

 

 

 

 

 

 

 

Output Frequency Regulation, %

 

± 0.1

 

 

 

 

 

 

 

 

 

Output THDu at Nominal Voltage (Linear Load), %

 

<2%

 

 

 

 

 

 

 

 

Output THDu at nominal voltage Including a 100kVA Non Linear

 

 

2.5% (max)

 

 

Load per EN 62040-3, %

 

 

 

 

 

 

 

 

 

 

Capacity to Handle Step Load, %

 

 

0-100 or 100-0

 

 

 

 

 

Transient Recovery (Linear Loads), %, msec

within 5% peak to peak in one-line cycle

 

 

 

 

 

 

Capacity to Handle Leading PF Load

 

Up to 0.8 with the following ratings:

 

 

 

 

 

 

 

a - 0.5 lag to 0.9 lag

 

a - Subject to maximum kVA rating

 

 

 

 

 

 

 

b - 0.9 lag to Nom

 

b - Subject to maximum kW rating

 

 

 

 

 

 

 

c - at 0.95 Lead

 

c - Subject to maximum. kW rating

 

 

 

 

 

d - at 0.9 Lead

d - Subject to 12,5% kW derate or same rating

 

 

and 10°C temp. derate

 

 

 

 

 

 

e - at 0.8 Lead

e - Subject to 25% kW derate or 12,5% kW derate and

 

 

10°C Temp. Derate

 

 

 

 

 

 

Voltage Displacement, ° el

120° ±1° el (with 100% unbalanced load)

 

 

 

 

 

 

 

Compliance to FCC Class-A

 

 

Standard

 

 

 

 

 

 

 

 

 

110% for 60 minutes

 

 

 

 

 

 

 

Overload Conditions, % FL

 

125% for 10 minutes

 

 

 

 

 

 

 

 

 

 

 

150% for 1 minute

 

 

 

 

 

 

 

 

40