| SPECIFICATIONS | |
Table 6 | Electrical specifications |
|
|
|
|
|
|
|
|
|
|
| |
Liebert NXL Model Size | 250 |
| 300 |
| 400 | |
|
|
|
|
|
| |
Input Parameters |
|
|
|
|
| |
|
|
|
|
|
|
|
| Input Voltage to Rectifier, VAC |
| 480V |
| ||
|
|
|
|
| ||
| Input Voltage to Bypass, VAC |
| 480V |
| ||
|
|
|
|
|
| |
| Permissible Input Voltage Range, VAC |
|
| 70% to 110% |
| |
|
|
|
|
|
| |
| Input Frequency, Hz |
| 60 |
|
| |
|
|
|
|
|
| |
| Permissible Input Frequency Range, Hz |
|
| 55 to 65 |
| |
|
|
| ||||
| Input THDi at nominal voltage at full load, % | <10% with | ||||
|
|
|
|
|
| |
| Input Power Factor at nominal voltage |
| >= 0.92 |
|
| |
|
|
| ||||
| Flexi Power | 3 to 30 (selectable) in 1 sec. Increments | ||||
|
|
|
|
|
| |
Battery & DC Parameters |
|
|
|
|
| |
|
|
|
|
| ||
| Battery Type | VRLA (Valve Regulated Lead Acid) or FLA | ||||
|
| (Flooded Lead Acid) |
| |||
|
|
|
| |||
| Nominal Battery Bus, VDC |
|
| 480V |
| |
|
|
|
|
|
| |
| Battery Float Voltage, VDC |
|
| 540V |
| |
|
|
|
|
| ||
|
| 384 (for VRLA / FLA) |
| |||
|
|
|
|
| ||
| DC Ripple Voltage in float & Const V Ch.mode, % |
| <1 (RMS value) < 3.4% Vpp |
| ||
|
|
|
|
| ||
| Temperature Compensated Battery Charging |
| Standard (with temperature probe) |
| ||
|
|
|
|
|
| |
Output Parameters |
|
|
|
|
| |
|
|
|
|
| ||
| Inverter Type | |||||
|
|
|
|
|
| |
| Output Power, kW | 225 |
| 270 |
| 360 |
|
|
|
|
|
|
|
| Output Voltage |
|
| 480VAC, |
| |
|
|
|
|
| ||
| Output Voltage Regulation, % |
| < 1% |
| ||
|
|
|
|
| ||
| Output Voltage Regulation (100% Unb. Load) |
| < 2% |
| ||
|
|
|
|
|
| |
| Output Frequency, Hz |
| 60 |
|
| |
|
|
|
|
|
| |
| Output Frequency Regulation, % |
| ± 0.1 |
|
| |
|
|
|
|
|
| |
| Output THDu at Nominal Voltage (Linear Load), % |
| <2% |
|
| |
|
|
|
|
|
| |
Output THDu at nominal voltage Including a 100kVA Non Linear |
|
| 2.5% (max) |
| ||
| Load per EN |
|
|
| ||
|
|
|
|
|
| |
| Capacity to Handle Step Load, % |
|
|
| ||
|
|
| ||||
| Transient Recovery (Linear Loads), %, msec | within 5% peak to peak in | ||||
|
|
|
|
| ||
| Capacity to Handle Leading PF Load |
| Up to 0.8 with the following ratings: |
| ||
|
|
|
|
| ||
| a - 0.5 lag to 0.9 lag |
| a - Subject to maximum kVA rating |
| ||
|
|
|
|
| ||
| b - 0.9 lag to Nom |
| b - Subject to maximum kW rating |
| ||
|
|
|
|
| ||
| c - at 0.95 Lead |
| c - Subject to maximum. kW rating |
| ||
|
|
| ||||
| d - at 0.9 Lead | d - Subject to 12,5% kW derate or same rating | ||||
|
| and 10°C temp. derate |
| |||
|
|
|
| |||
| e - at 0.8 Lead | e - Subject to 25% kW derate or 12,5% kW derate and | ||||
|
| 10°C Temp. Derate |
| |||
|
|
|
| |||
| Voltage Displacement, ° el | 120° ±1° el (with 100% unbalanced load) | ||||
|
|
|
|
|
| |
| Compliance to FCC |
|
| Standard |
| |
|
|
|
|
| ||
|
|
| 110% for 60 minutes |
| ||
|
|
|
|
| ||
| Overload Conditions, % FL |
| 125% for 10 minutes |
| ||
|
|
|
|
|
| |
|
|
|
| 150% for 1 minute |
| |
|
|
|
|
|
|
|
40