| UPS Alarm and Status Messages | |
Table 7 | Liebert NXL alarm and status messages (continued) | |||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
| An active Input Current Limit alarm means the | Press “SILENCE” to silence the audible alarm. | |
|
| detected input current (RMS) exceeds the limit | ||
|
| setpoint (default is 125%). This may be normal | Observe the meters on the | |
|
| depending on various operating conditions, such | input voltage level, battery charge/discharge | |
Input Current Limit | as input voltage level, output load level, and | current, and output load percentage kW. Investigate | ||
|
| whether the batteries have recently discharged. | any abnormal readings. | |
|
| This alarm is | If the reason for the alarm cannot be determined, | |
|
| no longer present, the alarm and any control | contact your | |
|
| activity tied to the alarm reverts to normal. |
| |
Input Disconnect | The rectifier disconnect device indicates that it is |
| ||
(Q1) Open |
| in the open position. |
| |
Input Disconnect | The externally mounted input isolator indicates |
| ||
(Q11) Open |
| that it is in the open position. |
| |
|
| The Input Filter Disconnect is locked open. |
| |
|
| The Input Filter Disconnect Cycle counter has | Press “SILENCE” to silence the audible alarm. | |
|
| exceeded the setpoint. The Input Filter | ||
|
| Disconnect opens automatically as determined by | Attempt to manually close the disconnect by | |
|
| the disconnect settings, or because of an unusual | pressing “Startup,” “Device Control,” “Close Trap.” | |
Input Filter Cycle | condition. | If the condition which caused the filter disconnect to | ||
An example of a setting would be to automatically | lock open is still present, it | |||
|
| |||
|
| open the filter disconnect under light load | If the disconnect cannot be manually closed or the | |
|
| conditions to improve the input power factor. An | alarm cannot be cleared, contact your factory- | |
|
| example of an unusual condition would be | authorized service provider. | |
|
| unbalanced currents on the input, possibly |
| |
|
| because of a suspect component in the filter itself. |
| |
|
| This summary alarm means there is a problem | Press “SILENCE” to silence the audible alarm. | |
|
| with input power. It is not acceptable to the | ||
|
| Rectifier. | Examine the | |
Input Not Avail | If the unit is running normally when this event | line feeding the Input Breaker should be green. If | ||
occurs, the UPS goes to battery. | not, investigate source power to the UPS. | |||
|
| |||
|
| This alarm is | If input power is good, and this alarm is active, | |
|
| no longer present, the alarm and any control | contact your | |
|
| activity tied to the alarm reverts to normal. |
| |
|
| This is a summary event caused by an |
| |
|
| interruption in communication between the |
| |
|
| controls and a device on the Controller Area |
| |
|
| Network (CAN). | Press “SILENCE” to silence the audible alarm. | |
|
| The Internal Communication Error event indicates | ||
Internal Comm | Press “RESET” to clear the alarm. | |||
a loss of communications between the controls | If the alarm cannot be reset, or if the alarm condition | |||
Error |
| and an external device. | ||
| returns, contact your | |||
|
| The Internal Communication Error is displayed | ||
|
| provider. | ||
|
| when the controls detect a loss of communication | ||
|
| to a device on the Controller Area Network (CAN). |
| |
|
| An infrequent occurrence that resets immediately |
| |
|
| is probably not serious. |
| |
|
| An overload condition is active on A phase. | Press “SILENCE” to silence the audible alarm. | |
|
| A phase load condition exceeds 105%. | ||
|
| Check the Module Output Meter and note the A | ||
|
| A countdown timer is displayed on the | ||
|
| phase load percentage. | ||
|
| Display in response to this alarm, and indicates | ||
|
| If possible, reduce A phase loading. | ||
|
| the time remaining until a transfer to bypass | ||
|
| If the steady state load remains above 105%, allow | ||
Inv Overload Ph A | occurs. The length of time remaining until transfer | |||
the UPS to transfer to bypass and contact your | ||||
|
| is directly proportional to the severity of the | ||
|
| overload. | ||
|
| If the displayed load percentage is less than 100% | ||
|
| This alarm is | ||
|
| and the alarm is still active, contact your factory- | ||
|
| no longer present, the alarm and any control | ||
|
| authorized service provider. | ||
|
| activity tied to the alarm reverts to normal. | ||
|
|
| ||
|
|
|
|