| UPS Alarm and Status Messages | |
Table 7 | Liebert NXL alarm and status messages (continued) | |||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
|
| To attempt to identify which sensor is reporting an | |
|
|
| inconsistent temperature or an overheating battery, | |
|
|
| observe the temperature reading inside the Battery | |
|
| With more than one Battery Temperature Sensor | Box on the | |
Batt Temp |
| installed, the controls are detecting too great a | connected batteries by pressing the Battery Box. | |
Imbalance |
| temperature difference between the individual | If it appears this alarm is due to a specific cabinet or | |
|
| sensors. | battery string being warmer than the others, verify | |
|
|
| through investigation whether the string is actually | |
|
|
| getting warmer than the others, or if the sensor | |
|
|
| appears to be reporting incorrectly. | |
|
|
| Contact your | |
|
| An Automatic or Manual Battery Test Failed. The |
| |
|
| battery “Test Duration” is adjustable. The battery |
| |
|
| test fail criteria were met before the end of the | Press “SILENCE” to silence the audible alarm. | |
Batt Test Failed | timed battery test. | |||
Contact your | ||||
|
| For example, there must be at least 25% load to | ||
|
|
| ||
|
| run the battery test. If, during the battery test the |
| |
|
| load drops below 25%, the test fails. |
| |
|
|
| Check the Active Event Window and investigate | |
|
|
| other events to further analyze. | |
|
| The conditions required to perform an automatic | If there are other active events in the Active Event | |
|
| battery test are not met. | Window, press “RESET” to clear the events. | |
|
| When the battery test is inhibited, the system | Check the | |
|
| delays the test for 7 days. If conditions are | online. | |
Batt Test Inhibit | satisfied after 7 days, the UPS performs the | Check the Module Output Meter and verify the kW | ||
|
| battery test at that time. | load is between | |
|
| Examples of conditions required to run the | Press the Battery Box on the | |
|
| automatic battery test are at least 20% load, all | verify all battery strings show at least 90% charged | |
|
| battery breakers closed, normal operation, etc. | and all battery breakers are closed. | |
|
|
| If the issue cannot be resolved, contact your | |
|
|
| ||
Batt Test Passed | The Battery Test passed. | None. | ||
|
|
|
| |
|
| The Backfeed Breaker is open. |
| |
|
| The Backfeed Breaker feeds the Static Bypass |
| |
|
| Switch (BPSS). The physical location of the |
| |
|
| breaker depends on unit configuration. It may be |
| |
|
| located in the UPS, or it may be located external | This status message is informational. If the breaker | |
|
| to the UPS. | ||
|
| was not opened intentionally, or if the breaker is | ||
BFB Open |
| The purpose of the Backfeed Breaker is to | ||
| actually closed and this message is active, contact | |||
|
| prevent leakage current through the bypass circuit | ||
|
| during an outage. | your | |
|
| This status message is |
| |
|
| condition is no longer present, the message and |
| |
|
| any control activity tied to the status event reverts |
| |
|
| to normal. |
| |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
| The Bypass Static Switch (BPSS) was turned off | If CB3 is available (visible if present on the One- | |
|
| due to an extended overload. | Line Display), close it to restore power to the load. | |
|
| While the BPSS can sustain an overload greater | DO NOT ATTEMPT TO CLOSE CB3 UNTIL THE | |
|
| than the Inverter and for a longer period of time, | SOURCE OF THE OVERLOAD IS IDENTIFIED | |
BPSS Ovld |
| there are still limits on the amplitude and duration | AND ISOLATED. | |
Exceeded |
| of overload that the BPSS can handle. This alarm | Once the overload source is isolated, restart the | |
|
| indicates the overload was greater in amplitude | UPS by pressing “Startup,” “Manual Start” and | |
|
| and time than the BPSS can handle, and | follow the prompts. | |
|
| therefore shut off to prevent damage to the | If the overload condition does not clear, or the | |
|
| equipment. | overload is cleared but the UPS does not restart, | |
|
|
| contact your | |
BPSS Unable | A problem has been detected in the Bypass Static | Press “SILENCE” to silence the audible alarm. | ||
Press “RESET” to attempt to clear the fault. | ||||
|
| Switch. | Contact your | |
|
|
| ||
|
|
|
|
46