Operation
2.3.6Remote Emergency Power Off
The Remote Emergency Power Off (REPO) mode will transfer the critical load to the bypass line and remove power from all UPS module components except the controls, bypass circuit breaker and the static switch.
The Remote Emergency Power Off control is a
When the Remote Emergency Power Off switch is operated, all UPS circuit breakers are opened, including the bypass circuit breaker. All power through the UPS is removed from the load. Typically, the REPO circuit also opens the circuit breakers that provide power to the bypass lines and the UPS controls. Refer to 2.5 - Shutdown Procedures.
Figure 29 Remote emergency power off
Bypass
BFB
Input
CB1
DC Bus |
CB2
Module Output
Battery System
MBD
2.4Manual Procedures
The Liebert NXL UPS is designed to function while unattended by an operator. Many important func- tions are handled automatically by the system control logic, as explained in 2.6 - Automatic Opera- tions. Other procedures must be performed manually.
Manual procedures available to the operator include Startup, Load Transfers and Shutdowns. These procedures are performed by using the touchscreen and some manually operated circuit breakers and switches.
The touchscreen lists all steps required for each manual procedure. This section lists
•
•Load
•Maintenance Bypass Load
•
NOTE
The following procedure assumes that the UPS installation inspection and initial startup have been performed by Liebert Services. A
23