UPS Alarm and Status Messages

Table 7

Liebert NXL alarm and status messages (continued)

 

 

 

Event Message

Event Definition

Recommended Action

 

 

With LBS operation enabled, conditions required

Press “SILENCE” to silence the audible alarm.

 

 

Check both Systems and verify normal operation:

 

 

to allow LBS operation are not met.

 

 

a. Both Systems running online on inverter;

 

 

Voltage or Frequency differences sensed by the

 

 

b. Neither System in Maintenance Bypass;

 

 

LBS control are preventing the ability of LBS to

LBS Inhibited

c. No Bypass, Input, or Synchronization errors

function correctly.

 

 

present on either system.

 

 

This alarm is self-clearing. When the condition is

 

 

If the cause of the alarm cannot be determined by

 

 

no longer present, the alarm and any control

 

 

checking both Systems, contact your factory-

 

 

activity tied to the alarm reverts to normal.

 

 

authorized service provider.

 

 

 

 

 

 

 

 

 

Load Bus Synchronization (LBS) is enabled and

 

 

 

is active.

 

 

 

This status message informs the user that one

Under normal circumstances, none.

 

 

system in an LBS system has lost its

LBS Operating

synchronization source (usually its own Bypass)

If this message is active, and there is no clear

and is now synchronized to the other system by

reason why the LBS circuit should be active, contact

 

 

 

 

the LBS controls.

your factory-authorized service provider.

 

 

This status message is self-clearing. When the

 

 

 

condition is no longer present, the alarm and any

 

 

 

control activity tied to the alarm reverts to normal.

 

 

 

With a load of 80% or greater, the controls have

 

 

 

calculated the output Power Factor to be less than

Press “SILENCE” to silence the audible alarm.

 

 

.95 leading.

Check the Output Meter readings and verify the

 

 

Leading Power Factors result in wasted energy. If

Leading Pwr

 

Output Power Factor. If the displayed power factor

 

the Power Factor is less than .95 leading, the

is less than .95 leading, and the load is greater than

Factor

 

UPS output is de-rated to compensate for output

 

80%, reduce the load or investigate.

 

 

losses.

 

 

Contact your factory-authorized service

 

 

This alarm is self-clearing. When the condition is

 

 

representative.

 

 

no longer present, the alarm and any control

 

 

 

 

 

activity tied to the alarm reverts to normal.

 

 

 

 

Load on Bypass

The load is being supplied by bypass.

None.

 

 

 

Load on Maint Byp

The load is on Maintenance Bypass.

None.

 

 

 

 

 

 

One or more battery circuit breakers are open.

 

 

 

This alarm applies if the system includes more

Press “SILENCE” to silence the audible alarm.

 

 

than one battery circuit breaker, and at least one

Low Batt Capacity

is closed, but one or more are open.

To clear this alarm, verify all battery breakers are

 

 

This alarm is self-clearing. When the condition is

closed. Investigate any open breakers.

 

 

no longer present, the alarm and any control

 

 

 

activity tied to the alarm reverts to normal.

 

 

 

The Battery has reached End of Discharge

Press “SILENCE” to silence the audible alarm.

 

 

(EOD).

 

 

Once power is restored, attempt a normal restart of

Low Batt

 

There is no longer enough energy left in the

 

the UPS.

Shutdown

 

battery to run the Inverter with the current load.

 

If the restart fails, contact your factory-authorized

 

 

If bypass is available, the UPS attempts to

 

 

service provider.

 

 

transfer the load to bypass at EOD.

 

 

 

 

 

 

 

 

 

 

Check to see if bypass is available by observing the

 

 

The battery is nearly depleted, and the unit shuts

One-Line Display. Acceptable bypass voltage is

 

 

down very soon.

indicated by a green power line feeding the Static

 

 

The Low Battery Warning setpoint is adjustable

Bypass Switch (BPSS) box.

Low Battery

 

under User Settings. This alarm means the

If bypass is available, press “Transfer,” “Bypass” to

 

calculated time remaining on battery is now less

transfer to bypass. If the bypass is qualified, the

Warning

 

 

than the Low Battery Warning setpoint.

UPS transfers to the bypass source.

 

 

 

 

This alarm is self-clearing. When the condition is

If bypass is not available, prepare to shut down

 

 

no longer present, the alarm and any control

critical loads, or remove non-essential loads in

 

 

activity tied to the alarm reverts to normal

order to extend battery run time so that critical loads

 

 

 

may be shut down in an orderly manner.