| UPS Alarm and Status Messages | |
Table 7 | Liebert NXL alarm and status messages (continued) | |||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
| With LBS operation enabled, conditions required | Press “SILENCE” to silence the audible alarm. | |
|
| Check both Systems and verify normal operation: | ||
|
| to allow LBS operation are not met. | ||
|
| a. Both Systems running online on inverter; | ||
|
| Voltage or Frequency differences sensed by the | ||
|
| b. Neither System in Maintenance Bypass; | ||
|
| LBS control are preventing the ability of LBS to | ||
LBS Inhibited | c. No Bypass, Input, or Synchronization errors | |||
function correctly. | ||||
|
| present on either system. | ||
|
| This alarm is | ||
|
| If the cause of the alarm cannot be determined by | ||
|
| no longer present, the alarm and any control | ||
|
| checking both Systems, contact your factory- | ||
|
| activity tied to the alarm reverts to normal. | ||
|
| authorized service provider. | ||
|
|
| ||
|
|
|
| |
|
| Load Bus Synchronization (LBS) is enabled and |
| |
|
| is active. |
| |
|
| This status message informs the user that one | Under normal circumstances, none. | |
|
| system in an LBS system has lost its | ||
LBS Operating | synchronization source (usually its own Bypass) | If this message is active, and there is no clear | ||
and is now synchronized to the other system by | reason why the LBS circuit should be active, contact | |||
|
| |||
|
| the LBS controls. | your | |
|
| This status message is |
| |
|
| condition is no longer present, the alarm and any |
| |
|
| control activity tied to the alarm reverts to normal. |
| |
|
| With a load of 80% or greater, the controls have |
| |
|
| calculated the output Power Factor to be less than | Press “SILENCE” to silence the audible alarm. | |
|
| .95 leading. | Check the Output Meter readings and verify the | |
|
| Leading Power Factors result in wasted energy. If | ||
Leading Pwr |
| Output Power Factor. If the displayed power factor | ||
| the Power Factor is less than .95 leading, the | is less than .95 leading, and the load is greater than | ||
Factor |
| UPS output is | ||
| 80%, reduce the load or investigate. | |||
|
| losses. | ||
|
| Contact your | ||
|
| This alarm is | ||
|
| representative. | ||
|
| no longer present, the alarm and any control | ||
|
|
| ||
|
| activity tied to the alarm reverts to normal. |
| |
|
|
| ||
Load on Bypass | The load is being supplied by bypass. | None. | ||
|
|
| ||
Load on Maint Byp | The load is on Maintenance Bypass. | None. | ||
|
|
|
| |
|
| One or more battery circuit breakers are open. |
| |
|
| This alarm applies if the system includes more | Press “SILENCE” to silence the audible alarm. | |
|
| than one battery circuit breaker, and at least one | ||
Low Batt Capacity | is closed, but one or more are open. | To clear this alarm, verify all battery breakers are | ||
|
| This alarm is | closed. Investigate any open breakers. | |
|
| no longer present, the alarm and any control |
| |
|
| activity tied to the alarm reverts to normal. |
| |
|
| The Battery has reached End of Discharge | Press “SILENCE” to silence the audible alarm. | |
|
| (EOD). | ||
|
| Once power is restored, attempt a normal restart of | ||
Low Batt |
| There is no longer enough energy left in the | ||
| the UPS. | |||
Shutdown |
| battery to run the Inverter with the current load. | ||
| If the restart fails, contact your | |||
|
| If bypass is available, the UPS attempts to | ||
|
| service provider. | ||
|
| transfer the load to bypass at EOD. | ||
|
|
| ||
|
|
|
| |
|
|
| Check to see if bypass is available by observing the | |
|
| The battery is nearly depleted, and the unit shuts | ||
|
| down very soon. | indicated by a green power line feeding the Static | |
|
| The Low Battery Warning setpoint is adjustable | Bypass Switch (BPSS) box. | |
Low Battery |
| under User Settings. This alarm means the | If bypass is available, press “Transfer,” “Bypass” to | |
| calculated time remaining on battery is now less | transfer to bypass. If the bypass is qualified, the | ||
Warning |
| |||
| than the Low Battery Warning setpoint. | UPS transfers to the bypass source. | ||
|
| |||
|
| This alarm is | If bypass is not available, prepare to shut down | |
|
| no longer present, the alarm and any control | critical loads, or remove | |
|
| activity tied to the alarm reverts to normal | order to extend battery run time so that critical loads | |
|
|
| may be shut down in an orderly manner. |
56