| UPS Alarm and Status Messages | |
Table 7 | Liebert NXL alarm and status messages (continued) | |||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
|
| Resolve the issue that precipitated the EPO. | |
|
|
| For safety, the UPS latches an EPO event. There | |
|
|
| are two ways to clear the latch: | |
|
|
| 1. Press the EPO Reset pushbutton on the External | |
|
|
| Interface Board (EIB). | |
|
| The UPS shuts down in response to an active | 2. From HMI front panel display, press OK button | |
EPO Shutdown | when ” Press OK to Reset EPO Latched signal” | |||
Emergency Power Off (EPO) command. | ||||
|
| message is displayed | ||
|
|
| ||
|
|
| in a dialog box. | |
|
|
| Verify the EPO is cleared by observing the EPO | |
|
|
| alarm in the Active Event Window is gone. | |
|
|
| Restart the UPS by pressing “Startup,” “Manual | |
|
|
| Start,” and follow the prompts. | |
|
|
|
| |
|
|
| Investigate possible causes for a rising temperature | |
|
|
| condition, such as loss of air conditioning, airflow | |
|
|
| obstructions, etc. If the ambient temperature is high | |
|
|
| due to loss of air conditioning and cannot be | |
|
| This summary event indicates the UPS is nearing | addressed immediately, perform the following: | |
|
| 1. Press “Transfer,” “Bypass” to transfer the UPS | ||
|
| an over temperature condition. Depending on | to bypass. | |
|
| which sensor is reporting the high temperature, | ||
|
| 2. Press “SILENCE” to silence the audible alarm. | ||
Equip Ovtemp | the UPS may do one of three things once the limit | |||
3. Wait at least 15 minutes, then attempt to reset | ||||
|
| is reached: shut down, transfer to bypass, or | the alarm by pressing “RESET.” | |
|
| transfer to battery operation. This is a potentially | ||
|
| 4. If the alarm clears and proper cooling has been | ||
|
| serious event. | ||
|
| restored to the UPS, press “Transfer,” “UPS” to | ||
|
|
| ||
|
|
| transfer back to UPS. | |
|
|
| If this alarm is present and no external factors are | |
|
|
| affecting proper cooling of the UPS, contact your | |
|
|
|
50