UPS Alarm and Status Messages

Table 7

Liebert NXL alarm and status messages (continued)

 

 

 

Event Message

Event Definition

Recommended Action

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

 

Resolve the issue that precipitated the EPO.

 

 

 

For safety, the UPS latches an EPO event. There

 

 

 

are two ways to clear the latch:

 

 

 

1. Press the EPO Reset pushbutton on the External

 

 

 

Interface Board (EIB).

 

 

The UPS shuts down in response to an active

2. From HMI front panel display, press OK button

EPO Shutdown

when ” Press OK to Reset EPO Latched signal”

Emergency Power Off (EPO) command.

 

 

message is displayed

 

 

 

 

 

 

in a dialog box.

 

 

 

Verify the EPO is cleared by observing the EPO

 

 

 

alarm in the Active Event Window is gone.

 

 

 

Restart the UPS by pressing “Startup,” “Manual

 

 

 

Start,” and follow the prompts.

 

 

 

 

 

 

 

Investigate possible causes for a rising temperature

 

 

 

condition, such as loss of air conditioning, airflow

 

 

 

obstructions, etc. If the ambient temperature is high

 

 

 

due to loss of air conditioning and cannot be

 

 

This summary event indicates the UPS is nearing

addressed immediately, perform the following:

 

 

1. Press “Transfer,” “Bypass” to transfer the UPS

 

 

an over temperature condition. Depending on

to bypass.

 

 

which sensor is reporting the high temperature,

 

 

2. Press “SILENCE” to silence the audible alarm.

Equip Ovtemp

the UPS may do one of three things once the limit

3. Wait at least 15 minutes, then attempt to reset

 

 

is reached: shut down, transfer to bypass, or

the alarm by pressing “RESET.”

 

 

transfer to battery operation. This is a potentially

 

 

4. If the alarm clears and proper cooling has been

 

 

serious event.

 

 

restored to the UPS, press “Transfer,” “UPS” to

 

 

 

 

 

 

transfer back to UPS.

 

 

 

If this alarm is present and no external factors are

 

 

 

affecting proper cooling of the UPS, contact your

 

 

 

factory-authorized service provider.

50

Page 56
Image 56
Emerson 250-400kVA manual Resolve the issue that precipitated the EPO