| UPS Alarm and Status Messages | |
|
|
|
| |
Table 7 | Liebert NXL alarm and status messages (continued) | |||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
| The Controls Communication Failure event |
| |
|
| indicates a loss of communications between the |
| |
|
| Controls and Human Machine Interface (HMI). | If the alarm does not clear, or if the alarm condition | |
Controls |
| The Controls Communication Failure event is | ||
| displayed when the HMI detects a loss of | returns, contact your | ||
Comm Fail |
| |||
| communication with Controls on the Controller | provider. | ||
|
| |||
|
| Area Network (CAN). |
| |
|
| An infrequent occurrence that resets immediately |
| |
|
| is probably not serious. |
| |
|
| This alarm means one or more critical settings |
| |
|
| have been changed by user during UPS |
| |
Controls Reset | operation. |
| ||
The change(s) will not take effect until after a UPS | Press “SILENCE” to silence the audible alarm. | |||
Required |
| |||
| Controls reset. This operation should only be |
| ||
|
|
| ||
|
| performed by an authorized service personnel. |
| |
|
| This alarm is cleared after UPS Controls reset. |
| |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
|
| Press “RESET” to clear the fault. | |
|
| The negative DC Bus has a ground fault. | Perform a visual inspection of the batteries. Look for | |
|
| The UPS controls monitor the DC Bus negative | signs of leaking battery acid or excessively | |
|
| half for a voltage imbalance caused by current | corroded battery terminals. | |
|
| flow to ground. This fault means excessive | If there are no visible signs of defective batteries, | |
DC Link |
| ground current is detected. | open one Battery Breaker. Press “RESET” and see | |
| In normal operation, with the batteries connected, | if the condition clears. If the condition clears, you | ||
Gnd Fault - |
| |||
| the most likely cause of a current path to ground | have isolated the problem to that battery string. | ||
|
| |||
|
| is a leaking battery. | If the condition will not clear, repeat the test with | |
|
| If your system includes an optional Battery | each connected battery string. | |
|
| Ground Fault Monitor, check if the Battery Ground | Once the location is identified, or if the battery string | |
|
| Fault message is present also. | tests are inconclusive, contact your factory- | |
|
|
| authorized service provider. | |
|
|
|
| |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
| The positive DC Bus has a ground fault. | Press “RESET” to clear the fault. | |
|
| Perform a visual inspection of the batteries. Look for | ||
|
| The UPS controls monitor the DC Bus positive | ||
|
| signs of leaking battery acid or excessively | ||
|
| half for a voltage imbalance caused by current | ||
|
| corroded battery terminals. | ||
|
| flow to ground. This fault means excessive | ||
|
| If there are no visible signs of defective batteries, | ||
|
| ground current is detected. | ||
DC Link |
| open one Battery Breaker. Press “RESET” and see | ||
| In normal operation, with the batteries connected, | |||
Gnd Fault + |
| the most likely cause of a current path to ground | if the condition clears. If the condition clears, you | |
|
| have isolated the problem to that battery string. | ||
|
| is a leaking battery. | ||
|
| If the condition will not clear, repeat the test with | ||
|
| If your system includes an optional Battery | ||
|
| each connected battery string. | ||
|
| Ground Fault Monitor, check if the Battery Ground | ||
|
| Once the location is identified, or if the battery string | ||
|
| Fault message is present also. | tests are inconclusive, contact your factory- | |
|
|
| authorized service provider. | |
|
|
|
| |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
| An Emergency Module Off (EMO) command has | Resolve the issue that precipitated the EMO. | |
|
| For safety, the UPS latches an EPO event. To clear | ||
|
| been detected. | ||
|
| the latch, press the EMO Reset pushbutton on the | ||
|
| The EMO signal means the front panel EMO | ||
|
| External Interface Board (EIB). | ||
EMO Shutdown | button was pressed. A Remote EMO would | |||
Verify the EMO is cleared by pressing “RESET” and | ||||
|
| display the “REMO Shutdown” alarm. | ||
|
| observing that the EPO alarm in the Active Event | ||
|
| In response to an EMO, the UPS transfers to | ||
|
| Window is gone. | ||
|
| Bypass and shuts off. | ||
|
| Restart the UPS by pressing “Startup,” “Manual | ||
|
|
| ||
|
|
| Start,” and follow the prompts. | |
|
|
|
|
49