|
|
| UPS Alarm and Status Messages | |
|
|
|
| |
Table 7 | Liebert NXL alarm and status messages (continued) | |||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
| An overload condition is active on B phase. | Press “SILENCE” to silence the audible alarm. | |
|
| B phase load condition exceeds 105%. | ||
|
| Check the Module Output Meter and note the B | ||
|
| A countdown timer is displayed on the | ||
|
| phase load percentage. | ||
|
| Display in response to this alarm, and indicates | ||
|
| If possible, reduce B phase loading. | ||
|
| the time remaining until a transfer to bypass | ||
|
| If the steady state load remains above 105%, allow | ||
Inv Overload Ph B | occurs. The length of time remaining until transfer | |||
|
| is directly proportional to the severity of the | the UPS to transfer to bypass and contact your | |
|
| |||
|
| overload. | ||
|
| If the displayed load percentage is less than 100% | ||
|
| This alarm is | ||
|
| and the alarm is still active, contact your factory- | ||
|
| no longer present, the alarm and any control | ||
|
| authorized service provider. | ||
|
| activity tied to the alarm reverts to normal. | ||
|
|
| ||
|
|
|
| |
|
| An overload condition is active on C phase. | Press “SILENCE” to silence the audible alarm. | |
|
| C phase load condition exceeds 105%. | ||
|
| Check the Module Output Meter and note the C | ||
|
| A countdown timer is displayed on the | ||
|
| phase load percentage. | ||
|
| Display in response to this alarm, and indicates | ||
|
| If possible, reduce C phase loading. | ||
|
| the time remaining until a transfer to bypass | ||
|
| If the steady state load remains above 105%, allow | ||
Inv Overload Ph C | occurs. The length of time remaining until transfer | |||
|
| is inversely proportional to the severity of the | the UPS to transfer to bypass and contact your | |
|
| |||
|
| overload. | ||
|
| If the displayed load percentage is less than 100% | ||
|
| This alarm is | ||
|
| and the alarm is still active, contact your factory- | ||
|
| no longer present, the alarm and any control | ||
|
| authorized service provider. | ||
|
| activity tied to the alarm reverts to normal. | ||
|
|
| ||
|
|
|
| |
|
| This message is displayed in response to an |
| |
|
| overload on one or more output phases. | Press “SILENCE” to silence the audible alarm. | |
|
| When an overload occurs, the controls display a | ||
|
| countdown timer that displays the time remaining | Observe the load percentages for each phase on | |
|
| until a transfer to bypass occurs. The length of the | the Module Output Meter. If the load is less than | |
|
| timer is inversely proportional to the amplitude of | 100%, attempt to transfer back to Inverter by | |
Inv Ovld Exceeded | the overload. When the timer reaches zero, the | pressing “Transfer,” “UPS.” | ||
|
| UPS transfers to bypass and populates the Active | If the transfer is successful, investigate the reason | |
|
| Event Window with this alarm. | for the overload and take appropriate action. | |
|
| This fault is | If the transfer is unsuccessful, contact your factory- | |
|
| condition is no longer present, this fault and any | authorized service provider. | |
|
| control activity tied directly to this fault reverts to |
| |
|
| normal. |
| |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
|
| Check the | |
|
|
| of the UPS. If both the Rectifier and Inverter are | |
|
|
| shut off, press “RESET” to attempt to clear any | |
|
|
| latched alarms or faults. | |
|
| This summary event indicates a potentially | Attempt a restart by pressing “Startup,” “Manual | |
|
| serious problem in the Inverter. | Start,” and follow the prompts to place the UPS | |
|
| The controls react to an Inverter fault in different | back in service. | |
Inverter Fault | ways depending on the root event that caused the | If the startup fails, contact your | ||
|
| fault. If bypass is available, the controls transfer to | service provider. | |
|
| static bypass. | If the Rectifier and Inverter appear to be running, | |
|
| A restart may or may not be possible | press “RESET” to attempt to clear any latched | |
|
|
| alarms or faults, then attempt a transfer by pressing | |
|
|
| “Transfer,” “UPS.” If the transfer is successful, | |
|
|
| contact your | |
|
|
| If the transfer is unsuccessful, contact your factory- | |
|
|
| authorized service provider. | |
|
| The controls have detected voltage on the |
| |
|
| Inverter (Line side) side of the Inverter Static | Press “SILENCE” to silence the audible alarm. | |
|
| Switch. | ||
|
| Turn off Control Power to clear the event. Wait 5 | ||
|
| This indicates that an SCR is shorted. | ||
ISS SCR Shorted | minutes before | |||
With the Output SCRs turned off, there should be | ||||
|
| no voltage present inside the UPS. | If the fault fails to clear, contact your factory- | |
|
| authorized service representative. | ||
|
| This is a | ||
|
|
| ||
|
| normal start up of the UPS. |
| |
|
|
|
|
55