| UPS Alarm and Status Messages | |
Table 7 | Liebert NXL alarm and status messages (continued) | |||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
|
| Observe the calculated load percentage on C phase | |
|
|
| displayed on the Module Output Meter. If the | |
|
| The critical load is greater than 110% while the | C phase steady state load percentage exceeds | |
|
| 110%, perform the following: | ||
|
| UPS is on bypass. The controls may shut the unit | ||
|
| If Maintenance Bypass is available, follow Standard | ||
|
| down if the overload condition does not clear | Operating Procedures to transfer the load to | |
|
| within the allotted time. Allotted time is variable, | ||
|
| Maintenance Bypass. | ||
|
| and is inversely proportional to the amplitude of | ||
Byp Overload | If Maintenance Bypass is not available but the | |||
the overload, i.e., the greater the amplitude of the | ||||
Ph C |
| system has an Internal Bypass Breaker (CB3 on the | ||
|
| overload, the less time the unit continues to | ||
|
| support the load. | ||
|
| on the severity of the overload, the possibility exists | ||
|
| This alarm is | ||
|
| that CB3 could trip if the overload exceeds the | ||
|
| no longer present, the alarm and any control | ||
|
| breaker rating. | ||
|
| activity tied to the alarm reverts to normal. | ||
|
| Investigate the overload condition. | ||
|
|
| ||
|
|
| If the Module Output Meter does not indicate an | |
|
|
| overload condition, perform the previous steps and | |
|
|
| contact your | |
Bypass Breaker | The bypass circuit breaker has failed to respond |
| ||
(CB3) Close Fail | to a close signal. |
| ||
Bypass Breaker | The bypass circuit breaker has failed to respond |
| ||
(CB3) Open Fail | to an open signal. |
| ||
Bypass Line Fail | The bypass source is not present. |
| ||
|
|
|
| |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
|
| Observe the | |
|
|
| line feeding the static switch is green when bypass | |
|
|
| power is within normal operating range. If the line | |
|
|
| feeding the static switch is orange, gray, or black, | |
|
| This summary event indicates a problem with the | bypass voltage is out of tolerance. Also check the | |
|
| detected bypass voltage. If bypass is not | bypass voltage readings on the Bypass Meter. | |
Bypass Not Avail | available, transfers to bypass are disabled. | When the bypass returns to normal, this alarm | ||
This alarm is | clears automatically. If all indications checked | |||
|
| |||
|
| no longer present, the alarm and any control | above are normal and the alarm is still present, | |
|
| activity tied to the alarm reverts to normal. | contact your | |
|
|
| If there is a problem indicated with the bypass | |
|
|
| voltage, investigate and resolve the issue. | |
|
|
| Examples of conditions that could cause this alarm: | |
|
|
| Unstable generator voltage; or, Bypass Feeder | |
|
|
| Breaker tripped. | |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
| The bypass frequency has exceeded the bypass | Check the frequency on the Bypass Meter. If the | |
|
| frequency is outside the synchronization range, | ||
|
| frequency limit of ± 5 Hz of nominal. If this alarm is | ||
|
| investigate and resolve the issue. | ||
Bypass OF/UF | active, transfers to bypass are disabled. | This alarm is commonly the result of an uncalibrated | ||
This alarm is | ||||
|
| generator, or power anomalies on the utility feed. | ||
|
| no longer present, the alarm and any control | ||
|
| Check bypass power for nominal limits. | ||
|
| activity tied to the alarm reverts to normal. | ||
|
| If bypass frequency appears normal, contact your | ||
|
|
| ||
|
|
| ||
|
|
|
| |
|
| This is a summary event that indicates a DSP |
| |
|
| communication error. | Press “SILENCE” to silence the audible alarm. | |
Controller Error | The Controller Error event is a fault condition that | Press “RESET” to attempt to reset the fault. | ||
|
| indicates a loss of communications in the | Contact your | |
|
| controls. |
|