UPS Alarm and Status Messages

Table 7

Liebert NXL alarm and status messages (continued)

 

 

 

Event Message

Event Definition

Recommended Action

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

 

Observe the calculated load percentage on C phase

 

 

 

displayed on the Module Output Meter. If the

 

 

The critical load is greater than 110% while the

C phase steady state load percentage exceeds

 

 

110%, perform the following:

 

 

UPS is on bypass. The controls may shut the unit

 

 

If Maintenance Bypass is available, follow Standard

 

 

down if the overload condition does not clear

Operating Procedures to transfer the load to

 

 

within the allotted time. Allotted time is variable,

 

 

Maintenance Bypass.

 

 

and is inversely proportional to the amplitude of

Byp Overload

If Maintenance Bypass is not available but the

the overload, i.e., the greater the amplitude of the

Ph C

 

system has an Internal Bypass Breaker (CB3 on the

 

 

overload, the less time the unit continues to

One-Line Display), close CB3. Note that depending

 

 

support the load.

 

 

on the severity of the overload, the possibility exists

 

 

This alarm is self-clearing. When the condition is

 

 

that CB3 could trip if the overload exceeds the

 

 

no longer present, the alarm and any control

 

 

breaker rating.

 

 

activity tied to the alarm reverts to normal.

 

 

Investigate the overload condition.

 

 

 

 

 

 

If the Module Output Meter does not indicate an

 

 

 

overload condition, perform the previous steps and

 

 

 

contact your factory-authorized service provider.

Bypass Breaker

The bypass circuit breaker has failed to respond

 

(CB3) Close Fail

to a close signal.

 

Bypass Breaker

The bypass circuit breaker has failed to respond

 

(CB3) Open Fail

to an open signal.

 

Bypass Line Fail

The bypass source is not present.

 

 

 

 

 

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

 

Observe the One-Line Display. The bypass power

 

 

 

line feeding the static switch is green when bypass

 

 

 

power is within normal operating range. If the line

 

 

 

feeding the static switch is orange, gray, or black,

 

 

This summary event indicates a problem with the

bypass voltage is out of tolerance. Also check the

 

 

detected bypass voltage. If bypass is not

bypass voltage readings on the Bypass Meter.

Bypass Not Avail

available, transfers to bypass are disabled.

When the bypass returns to normal, this alarm

This alarm is self-clearing. When the condition is

clears automatically. If all indications checked

 

 

 

 

no longer present, the alarm and any control

above are normal and the alarm is still present,

 

 

activity tied to the alarm reverts to normal.

contact your factory-authorized service provider.

 

 

 

If there is a problem indicated with the bypass

 

 

 

voltage, investigate and resolve the issue.

 

 

 

Examples of conditions that could cause this alarm:

 

 

 

Unstable generator voltage; or, Bypass Feeder

 

 

 

Breaker tripped.

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

The bypass frequency has exceeded the bypass

Check the frequency on the Bypass Meter. If the

 

 

frequency is outside the synchronization range,

 

 

frequency limit of ± 5 Hz of nominal. If this alarm is

 

 

investigate and resolve the issue.

Bypass OF/UF

active, transfers to bypass are disabled.

This alarm is commonly the result of an uncalibrated

This alarm is self-clearing. When the condition is

 

 

generator, or power anomalies on the utility feed.

 

 

no longer present, the alarm and any control

 

 

Check bypass power for nominal limits.

 

 

activity tied to the alarm reverts to normal.

 

 

If bypass frequency appears normal, contact your

 

 

 

 

 

 

factory-authorized service provider.

 

 

 

 

 

 

This is a summary event that indicates a DSP

 

 

 

communication error.

Press “SILENCE” to silence the audible alarm.

Controller Error

The Controller Error event is a fault condition that

Press “RESET” to attempt to reset the fault.

 

 

indicates a loss of communications in the

Contact your factory-authorized service provider.

 

 

controls.

 

48

Page 54
Image 54
Emerson 250-400kVA manual Displayed on the Module Output Meter. If