Emerson Process Management GmbH & Co. OHG 9-19
X-STREAM XE
Instruction Manual
HASXEE-IM-HS
04/2010
9Modbus Commands
9.3 List of Parameters and Registers - Sorted by Tag Name
Tag Name Address Data
Type
Client
Access Description
Modicon Daniel
Setup.In/Outputs.AO.AdjustEnd4 6391…
6392 9196 Float R/W ne adjustment for end range of out-
put4
Setup.In/Outputs.AO.AdjustEnd5 6399…
6400 9200 Float R/W ne adjustment for end range of out-
put5
Setup.In/Outputs.AO.AdjustStart1 6365…
6366 9183 Float R/W ne adjustment for start range of
output1
Setup.In/Outputs.AO.AdjustStart2 6373…
6374 9187 Float R/W ne adjustment for start range of
output2
Setup.In/Outputs.AO.AdjustStart3 6381…
6382 9191 Float R/W ne adjustment for start range of
output3
Setup.In/Outputs.AO.AdjustStart4 6389…
6390 9195 Float R/W ne adjustment for start range of
output4
Setup.In/Outputs.AO.AdjustStart5 6397…
6398 9199 Float R/W ne adjustment for start range of
output5
Setup.In/Outputs.AO.AutoScale1 3273 3273 Word R/W Auto scale for ranged signals on out-
put1 (0=NO, 1=Yes)
Setup.In/Outputs.AO.AutoScale2 3278 3278 Word R/W Auto scale for ranged signals on out-
put2 (0=NO, 1=Yes)
Setup.In/Outputs.AO.AutoScale3 3283 3283 Word R/W Auto scale for ranged signals on out-
put3 (0=NO, 1=Yes)
Setup.In/Outputs.AO.AutoScale4 3288 3288 Word R/W Auto scale for ranged signals on out-
put4 (0=NO, 1=Yes)
Setup.In/Outputs.AO.AutoScale5 3293 3293 Word R/W Auto scale for ranged signals on out-
put5 (0=NO, 1=Yes)
Setup.In/Outputs.AO.EndRange1 6363…
6364 9182 Float R/W level where analoge output scaling
ends on output1
Setup.In/Outputs.AO.EndRange2 6371…
6372 9186 Float R/W level where analoge output scaling
ends on output2
Setup.In/Outputs.AO.EndRange3 6379…
6380 9190 Float R/W level where analoge output scaling
ends on output3
Setup.In/Outputs.AO.EndRange4 6387…
6388 9194 Float R/W level where analoge output scaling
ends on output4
Setup.In/Outputs.AO.EndRange5 6395…
6396 9198 Float R/W level where analoge output scaling
ends on output5
Setup.In/Outputs.AO.FailMode1 3274 3274 Word R/W Behavior on errors output1 (0=Track,
1=-10%Start, 2=+10%End)
Setup.In/Outputs.AO.FailMode2 3279 3279 Word R/W Behavior on errors output2 (0=Track,
1=-10%Start, 2=+10%End)
Setup.In/Outputs.AO.FailMode3 3284 3284 Word R/W Behavior on errors output3 (0=Track,
1=-10%Start, 2=+10%End)
Setup.In/Outputs.AO.FailMode4 3289 3289 Word R/W Behavior on errors output4 (0=Track,
1=-10%Start, 2=+10%End)
Setup.In/Outputs.AO.FailMode5 3294 3294 Word R/W Behavior on errors output5 (0=Track,
1=-10%Start, 2=+10%End)
Setup.In/Outputs.AO.Hold1 3275 3275 Word R/W Hold output1 on calibrations (0=Track,
1=Hold)