Emerson VSG, VSSG manual Appendix E Recommended Remote Air Cooled Oil Cooler Piping, Outlet On Top

Models: VSG

1 106
Download 106 pages 24.52 Kb
Page 103
Image 103
OUTLET ON TOP

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

OUTLET ON TOP

 INLET ON BOTTOM INLET ON BOTTOM

Recommended location of drain connections as required.

Vertical drops should be no higher than 8 to 10 feet.

If there is no choice and the vertical drops need to be higher, then an electronic service valve needs to be installed in the return line at the compressor. Consult Factory.

If ambient temperatures get below 50° F, heat trace and insulation on oil lines and air cooler headers needs to be used.

Maximum pressure drop on oil lines to and from air cooler and compressor should not exceed anymore than 5 to 10 psi.

Appendix E • Recommended Remote Air Cooled Oil Cooler Piping

E

Page 103
Image 103
Emerson VSG, VSSG manual Appendix E Recommended Remote Air Cooled Oil Cooler Piping, Outlet On Top, Inlet On Bottom