Table 6-3. Troubleshooting Guide - General Problems & Solutions (1 of 3)

Section 6 • Troubleshooting

Table 6-3. Troubleshooting Guide - General Problems & Solutions (1 of 3)

Problem

Solution

 

After failing to start compressor with “Prelube Oil Pump Inhibit”, first allow

 

 

Discharge pressure, Oil Filter In pressure and Out pressure to equalize. Then

 

 

restart compressor. If compressor fails to start due to low oil pressure, contin-

 

 

ue troubleshooting with items below.

 

• Reset Prelube Oil Pressure Setpoint in Alarms and Trip Setpoints screen to

 

 

lowest recommended setpoints.

 

• Check calibration of oil manifold transducer, discharge pressure transducer,

 

 

and suction transducer.

Low Oil Pressure at Start

• Check for correct oil pump motor rotation and operation.

• Ensure transducer isolation valves are open.

 

 

• Verify that the correct transducer ranges are selected.

 

• Check to see all oil line valves are open except the oil dump valve used to fill

 

 

the lines and oil cooler.

 

• Check oil strainer for dirt.

 

• Check oil filter pressure drop.

 

• Check “Prelube Oil Pump Time Limit” setpoint is sufficient in Compressor

 

 

Timer Setpoints screen.

 

• Prelube pressure is manifold pressure minus discharge pressure.

 

• Check solutions in “Low Oil Pressure at Start”.

 

• Check that there is proper discharge pressure ratio to create differential pres-

 

 

sure, otherwise oil pressure can’t be maintained. Oil pressure is manifold oil

 

 

pressure minus the suction pressure. It is a net pressure.

Low Run Oil Pressure

• If the oil pump is selected to be a part time oil pump in the “Setup” menu,

 

then ensure that it only shuts off at an appropriate pressure ration that takes

 

 

 

 

into account pressure drops through the oil cooler. This is a set point in the

 

 

“Compressor Control Setpoints” menu called “Oil Pump Restart.” It is a pres-

 

 

sure ratio. (discharge pressure in psia/suction pressure in psia) Default ratio

 

 

is a pressure ratio of 3.00:1 that stops the pump and 2.80:1 that restarts the

 

 

pump. This ratio can be increased. Do not decrease without consulting Vilter.

 

• Clean oil strainer screen.

 

• Change oil filter, maybe plugged or collapsed.

Oil flow or oil pressure

Oil pump gears worn internally, excessive end-clearance.

problems

Oil priming valve used on air-cooled cooler units is open.

 

• Relief in-line check valve stuck open.

 

• Pressure ratio too low, oil pump should be on.

 

• Check that the correct pressure or temperature range is selected in the

Faulty pressure or temperature

 

Instrument Calibration menu.

• Check cable connections at device, terminal strips, and PLC input card for

readings

 

correct wiring and shielding (RF noise).

 

 

 

• Check calibration of RTDs and transducers.

 

 

 

 

 

 

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

6 – 5

Page 93
Image 93
Emerson VSG, VSSG manual 3. Troubleshooting Guide - General Problems & Solutions 1 of