Emerson VSSG, VSG manual Installation, Additional Information Codes and Standards

Models: VSG

1 106
Download 106 pages 24.52 Kb
Page 28
Image 28
Additional Information

Section 3 • Installation

Additional Information

Codes and Standards

Vilter followed the following codes and standards when designing your foundation:

ACI

ASTM

ASCE 7

IBC 2006

General Design Requirements

The compressor foundation is designed to:

Maintain the compressor in alignment and at proper elevation.

Minimize vibration and prevents its transmission to other structures

Provide a permanently rigid support

Operation and Performance

• Provide sufficient depth to dampen vibrations.

The foundation was designed for:

 

Outside environment severe exposure

Ambient temperature -10 degrees F to 105 degrees F

Unit weight 20,000 lbs

RPM 3600

Soil bearing capacity 1,500 lbs/sq.ft.

Wind speed 120 MPH

Exposure factor D

Wind importance factor 1.15

Concrete poured on and permanently cast against the earth

OVER ALL G.A. LENGTH + 4'-0"

10'-0"

5'-0"

CENTER LINE GAS COMPRESSION SYSTEM

Figure 3-5. Foundation with Housekeeping Pads Dimensions - Top View

3 – 8